Power consumption control
EPRA14~18DAV3+W1 + ETVH16SU18+23EA6V
Daikin Altherma 3 H HT F
4P644738-1 – 2021.02
In case the space heating/cooling request is OFF and the tank temperature
setpoint is reached, the unit can choose to buffer energy from the photovoltaic
panels in the room (only in case of room thermostat control) or in the DHW tank
instead of putting the photovoltaic panel energy on the grid.
In case of room buffering, the room will heat up or cool down to the comfort
setpoint. In case of tank buffering, the tank will heat up to the maximum tank
temperature.
The goal is to buffer the energy from the photovoltaic panels. Therefore, the
capacity of the unit is limited to what the photovoltaic panels are providing:
If Smart Grid pulse meter is...
Available
Not available
The safety functions (water pipe freeze prevention, drain prevention, room frost
protection, tank disinfection) and defrost are NOT overruled (capacity will not be
limited for these functions)
Forced on:
Similar to Recommended on, but there is no capacity limitation. The goal is NOT to
use the grid as much as possible.
Power consumption control
See
"6  Application
guidelines"  [
functionality.
#
[9.9.1]
[4-08]
[9.9.2]
[4-09]
Limit when [9.9.1]=Continuous and [9.9.2]=Amp:
#
[9.9.3]
[5-05]
Limits when [9.9.1]=Inputs and [9.9.2]=Amp:
Decided by the unit based on the input
of the Smart Grid pulse meter.
Decided by [9.8.8] Limit setting
kW
4
  34] for detailed information about this
Code
Power consumption control:
0 No: Disabled.
1 Continuous: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 Inputs: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
Type:
0 Amp: The limitation values are set in A.
1 kW: The limitation values are set in kW.
Code
Limit: Only applicable in case of full time
current limitation mode.
0 A~50 A
10
Configuration
|
Then the limit is...
Description
Description
Installer reference guide
207