(ON-OFF, CN2, Short Connector JR1)
NOTE:
Remove the short connector (JR1) when using the ON-OFF function.
Remote Switch
ON (close)
OFF (open)
1. Unit responds to demand; use the remote controller to select the required mode.
2. Unit will not respond to the demand from the remote controller.
NOTE:
If the remote switch is off, but the remote controller is on, the CP code appear on the display board.
NOTE:
The voltage of the port (CN2) is 12V DC; maximum current is 5mA.

4.5. Dial Codes

NOTE:
The SW4 DIP switch is for certified service technical use only.
No.
Dial Code
Control
Scenario
1
SW1-2
1,2
2
SW1-3
1,2,3
3
SW2-1
1
4
SW2-1
2
5
SW2-2
2
6
SW2-3
2
1
2
Function
Anti-cold blow protection option
Single cooling / heating and cooling options
Compressor Running (demand working with
heat pump+ Electric heat)
Temperature differential to activate first stage
auxiliary heat(the GAP of T1 and Ts),Wire
controller demand with heat pump+Electric heat
working together
Electric heat on delay
Electric auxiliary heating delay to start time
Unit Status
Unit is on.
Unit is off.
ON
NO
Cooling
Compressor
slower speed
2°F (1°C)
YES
30 minutes
26
Demand Response Time
Within two (2) seconds
Within two (2) seconds
OFF
[Default] YES
[Default] Cooling &
Heating
[Default] Faster
Only affects
Compressor
compressor and
[Default] 4°F (2°C)
[Default]NO
[Default] 15
Based on SW2-2
minutes
Note
W1
is ON