Siting The Appliance; Flue Terminal Position - Bosch WORCESTER 35CDi User, Installation And Servicing Instructions

Wall mounted combination boiler for central heating and mains fed domestic hot water
Hide thumbs Also See for WORCESTER 35CDi:
Table of Contents

Advertisement

4. Siting the Appliance

4.1. The appliance may be installed in any room but refer to the
requirements of the current IEE regulations and, in Scotland, the
relevant electrical provisions of the Building Regulations with
respect to the installation of appliances in rooms containing
baths or showers.
4.2. Where a room sealed appliance is installed in a room
containing a bath or shower, any switch or appliance control
using mains electricity must not be able to be touched by a
person using the bath or shower.
4.3. The appliance is NOT suitable for external installation
4.4. No special wall protection is required.
4.5. The wall must be able to support the weight of the
appliance. Refer to Table 4.
4.6. The specified clearances must be available for installation
and servicing. Refer to Table 8.
4.7. The appliance can be installed in a cupboard/compartment
to be used for airing clothes providing that the requirements of
BS6798 and BS5440/2 are followed. Refer to Section 2.4.6.
4.7.1. The airing space must be separated from the boiler space
by a perforated non-combustible partition. Expanded metal or
rigid wire mesh is acceptable provided that the major dimension
is less than 13mm.
4.7.2. The requirements for servicing space must be met when
an appliance is in a cupboard or compartment used for airing
clothes. Refer to Table 8.
4.7.3. The clearance between the front of the appliance and the
cupboard/compartment door should be not less than 75mm.
4.7.4. If the installed boiler is to be enclosed then the
requirements of BS6798 and BS5440:2 must be followed. Refer
to Section 2.4.6.
4.8. The pipe connection positions on the manifold are shown in
Fig. 4 and on wall template allowing the system to be pre-piped
and flushed before the appliance is fitted. Refer to Section 2.4.6.
4.8.1. Always consider the possibility that the pipes may need
to be separated from the appliance after installation.
4.9. LPG Installation. Refer to Section 1.10.
5. Flue Terminal Positions
5.1. The flue system must be installed following the
requirements of BS5440:1.
5.2. Standard flue length is 100 - 1000mm. An extension kit for
flues upto 2m is available.
Fig. 5. Flue Terminal Positions
Fig. 3. Casing Dimension and Clearances
35
500
Installation
25
5 or 25
Service
200
Fig. 4. Pipework Connections and Flue Position
500
322
A
252
B
235
C
206
D
203
E
144
F
98
G
55
H
A. Relief Valve Drain
B. Central Heating Return
C. Bypass Adjuster
D. Drain Point
E. Central Heating Flow
TERMINAL POSITION
A– Directly below an openable window or
other opening e.g. air brick.
B– Below gutters, soil pipes or drain pipes.
C– Below eaves.
D– Below balconies or car port roof.
E– From vertical drain pipes and soil pipes.
F– From internal or external corners.
G– Above ground, roof or balcony level.
H– From a surface facing a terminal.
I– From a terminal facing a terminal
J– From an opening in a car port (e.g. door
window) into dwelling.
K– Vertically from a terminal on the same
wall.
L– Horizontally from a terminal on the same
wall.
M– From door, window or air vent (achieve
where possible).
6
900
600
130
250
310
20
F. Cold Water In
G. Domestic Hot Water
Flow
H. Gas Inlet
MIN. DISTANCE
300 mm (12 in.)
75 mm (3 in.)
200 mm (8 in.)
200 mm (8 in.)
75 mm (3 in.)
300 mm (12 in.)
300 mm (12 in.)
600 mm (24 in.)
1200 mm (47 in.)
1200 mm (47 in.)
1500 mm (59 in.)
300 mm (12 in.)
150 mm (6 in.)
310
160

Advertisement

Table of Contents
loading

Table of Contents