Fujitsu ASYG12KGTE Service Manual page 69

Hide thumbs Also See for ASYG12KGTE:
Table of Contents

Advertisement

Check point 3. Check the solenoid coil and 4-way valve
NOTE: Refer solenoid coil and 4-way valve in
Solenoid coil
Remove P60 from PCB and check the resistance value of coil. Resistance value is 2.780 kΩ (at
20 °C).
If it is open or abnormal resistance value, replace solenoid coil.
4-way valve
Check each piping temperature, and the location of the valve by the temperature difference.
If the value location is not proper, replace 4-way valve.
Check point 4. Replace main PCB
If Check Point 1 to 4 do not improve the symptom, replace main PCB.
2-27. E: 99. 4-way valve error (Outdoor unit)
End
"Service parts information"
- (03-33) -
on page 03-43.
2. Troubleshooting with error code