APPENDIX A
Air Conditioner & Heat Pump with PURON

— Quick Reference Guide

S Puron
(R-410A) refrigerant operates at 50 percent to
70 percent higher pressures than R-22. Be sure that
servicing equipment and replacement components are
designed to operate with Puron.
S Puron refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400
psig, DOT 4BA400 or DOT BW400.
S Puron systems should be charged with liquid
refrigerant. Use a commercial type metering device in
the manifold hose when charging into suction line with
compressor operating.
S Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low-side retard.
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC
refrigerant.
S Puron, as with other HFCs, is only compatible with
POE oils.
S Vacuum pumps will not remove moisture from oil.
S Use only factory specified liquid-line filter driers with
rated working pressures greater than 600 psig.
S Do not install a suction-line filter drier in liquid-line.
S POE oils absorb moisture rapidly. Do not expose oil to
atmosphere.
S POE oils may cause damage to certain plastics and
roofing materials.
S Wrap all filter driers and service valves with wet cloth
when brazing.
S A factory approved, liquid-line filter drier is required on
every unit.
S Do not use an R-22 TXV.
S If indoor unit is equipped with a TXV, it must be
changed to a Puron
TXV.
S Never open system to atmosphere while it is under a
vacuum.
S When system must be opened for service, recover
refrigerant, break vacuum with dry nitrogen before
opening system.
S Always replace filter drier after opening system for
service.
S Do not vent Puron
into the atmosphere.
S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text.
S All Puron
heat pumps must have indoor TXV.
S Do not leave Puron
suction line driers in place for
more than 72 hours.

Wiring Diagram List

Unit
569J*08G/H
Low Ambient Option — Factory Installed
569J*08H units with the factory installed low ambient
option are equipped with a Motormaster
pressure control which regulates fan speed. A temperature
sensor mounted on the outdoor coil controls the speed of
approved outdoor fan motors in order to maintain a
constant head pressure in the outdoor coil (see Fig. 27).
The control maintains the appropriate head pressure at
low ambient temperatures down to - - 20_F (- - 28_C).
Fig. 27 - - 569J*08H Motormaster Sensor Location
29
APPENDIX B
Electrical
Diagram
Characteristics
Number
208/230---3---60
38AU000026
460---3---60
38AU000027
575---3---60
38AU000025
APPENDIX C
R
solid- - state head
C14297