c)
If the product is used in hazardous area, the installation, operation
and maintenance should comply with the operation manual and
relevant requirements of national standards.
d)
Be careful to tear down the instrument under the normal
atmospheric pressure.
3 Outline and installation
3.1 Product installation environment
3.1.1 Environmental condition
Operation Temperature:-40℃~85℃,With LCD display:-20℃~70℃
Storage Temperature:-40℃~100℃,With LCD display:-40℃~85℃
Ambient humidity range:5%RH~100%RH@40℃
3.1.2 Electromagnetic environment
Radiated interference:≤1000MHz
Radio frequency electromagnetic field interference≤10V/m(80MHz~
1GHz) ; Electrostatic interference≤8kV
Power frequency magnetic field interference≤30A/m
3.1.3
Installation location selection
a)
Please avoid locations subject to wide temperature variations or a
significant temperature gradient. And if the site equipment is
exposed to heat radiation, please take measures for insulation and
ventilation.
b)
It is not recommended to install the transmitter in the corrosive
environment. If it is unavoidable, ventilation measures must be
taken and be careful to prevent the rainwater from penetrating into
the cable lines.
c)
Although the transmitter is designed to be resistant to shock and
vibration. Try to install in places with low shock and vibration.
Warning
Avoid installation in places with large temperature differences, easy
condensation, easy icing and high vibration
2