Siemens st-h Operation Manual page 12

Hide thumbs Also See for st-h:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Mounting – Liquids Applications
Corrosive Applications
Blind Flange
Flange, gasket, and hardware
supplied by customer.
2" coupling welded
to tank top
Interconnection
Note: Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
For optimum isolation against electrical noise, run cable separately in a grounded metal
conduit with no other cabling (except temperature sensor). Ground shield only at
transceiver. Insulate shield at junctions to prevent inadvertent grounding.
Seal all thread connections to prevent ingress of moisture.
Do not route cable openly.
Do not run cable near high voltage or current runs, contactors, and SCR control drives.
Page EN-10
ST-H Transducer – OPERATION MANUAL
Coupling
Flanged
plastic type
coupling
Customer flanged
standpipe. If a metal
flange must be welded
to pipe, refer to the
Transducer Application
Manual
www.siemens.com/
processautomation
Coupling
Siemens
Milltronics
flange
adapter
. available at
7ML19985QK82

Advertisement

Table of Contents
loading

Table of Contents