Westinghouse WBRC 140W Series Installation Manual page 39

Gas fired residential combi boiler
Table of Contents

Advertisement

39
Figure 26 – CH Piping – Zoning with Pumps
NOTES:
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local
codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimum pipe size of DHW piping should be ¾" diameter and CH piping should be 1" in diameter.
5. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used
with circulator flanges as an alternative.
6. Piping shown is Primary/Secondary. System flow (secondary loop) must be greater than the appliance's primary loop flow.
7. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
8. VERY IMPORTANT – Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short
cycling.
9. Each heating zone of a pump-based system has its own circulator with turns on when a zone thermostat calls for heat.
10. Unit is equipped with built-in primary pump for the heating loop. This pump is sized to insure proper flow rate through the
appliance heat exchanger and related piping. On long pipe runs, it is recommended to keep the pump at maximum speed (setting 3).
DO NOT lower it from the factory default.
11. NOTE: DO NOT INSTALL a flow check or a pump with flow check on the return line of the primary loop going to the appliance. This
will isolate the appliance from the expansion tank, causing pressure to build up in the unit and the Pressure Relief Valve to discharge.
WHL-012 REV. 4.8.16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wbrc 199w series

Table of Contents