At commissioning and periodical checks, the functions shall be tested with the used settings.
To test a specific function, it might be necessary to change some setting parameters, for
example:
AutoEnerg = On / Off / DLLB / DBLL / Both
ManEnerg = Off
Operation = Off / On
Activation of the voltage selection function if applicable
The tests explained in the test procedures below describe the settings, which can be used as
references during testing before the final settings are specified. After testing, restore the
equipment to the normal or desired settings.
A secondary injection test set with the possibility to individually alter the phase angle and
amplitude of the voltage is needed. The test set must also be able to generate different
frequencies on different outputs.
Figure
17
description describes the test of the version intended for one bay.
Test
equipment
IEC08000027 V1 EN-US
Figure 17:
7.9.1.1

Testing the synchronizing function

This section is applicable only if the synchronizing function is included.
The voltage inputs used are:
ULine
U-Bus
Generator protection REG650
Commissioning manual
The description below applies for a system with a nominal frequency of 50 Hz
but can be directly transferred to 60 Hz. SESRSYN can be set to use different
phases, phase to earth or phase to phase. Use the set voltages instead of what
is indicated below.
shows the general test connection principle, which can be used during testing. This
IED
U-Bus
U-Line
N
General test connection with three-phase voltage connected to the line side
UL1, UL2 or UL3voltage inputs on the IED
Bus voltage input on the IED
© Copyright 2011 ABB. All rights reserved
U-Bus
UMeasure
N
Ph/N
Ph/Ph
UL1
Input Phase
UL2
L1,L2,L3
UL3
L12,L23,L31
N
en08000027.vsd
Section 7
Testing functionality
M2377-21 v5