Section 8
8.1
Commissioning and maintenance of the fault clearing
system
About this chapter
This chapter discusses maintenance tests and other periodic maintenance measures.
8.1.1

Installation and commissioning

The protection IED is in an on-guard situation where the IED can be inactive for several years
and then suddenly be required to operate within fractions of a second. This means that
maintenance testing with certain time intervals should be performed to detect failures of the
protection IED or the surrounding circuits. This is a complement to the advanced self
supervision in the modern protection IED.
IEDs are not expected to deteriorate with usage but extreme conditions, such as mechanical
shocks, AC or DC transients, high ambient temperatures, and high air humidity always have a
certain likelihood of causing damages.
Delivered equipment undergoes extensive testing and quality control in the ABB
manufacturing program. All types of IEDs and their integral components have been subject to
extensive laboratory testing during the development and design work. Prior to series
production of a specific IED, it is type tested according to national and international
standards. Each individual IED in normal production is individually tested and calibrated before
delivery.
Protection IEDs installed in an apparatus cubicle shall be checked in various ways before
delivery. Insulation test (to check for bad wiring) and complete testing of all equipment with
injection of currents and voltages is performed.
During the design of the station, certain steps shall be taken to limit the risk of failures, for
example, all IED coils are connected to negative potential to earth to prevent contact corrosion
due to electrolyte.
Certain circuits are continuously supervised to improve their availability. Examples of such
supervisions are:
Trip circuit supervision
Protection DC supply supervision
DC system earth fault supervision
Busbar protection CT-circuit supervision
Protection IEDs shall be encapsulated according to environment requirements. In tropical
climates, cubicles are provided with glass-door and ventilation louvres. Heaters for anti-
condensation, often thermostatically controlled, are provided. Cubicle power-loss is limited
not to exceed protection IED temperature limits, which is 55°C according to the IEC standard.
Generator protection REG650
Commissioning manual
Commissioning and maintenance of
the fault clearing system
© Copyright 2011 ABB. All rights reserved