8.3
Table 1 – Maximum refrigerant
charge allowed in a room: indoor
unit
2
A
(m
)
Maximum refrigerant charge in a room
room
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
INFORMATION
▪ For floorstanding models, the value of "Installation
height (H)" is considered 600  mm to comply to
IEC 60335-2-40:2013 A1 2016 Clause GG2.
▪ For intermediate A
between two values from the table), consider the value
that corresponds to the lower A
2
If A
=12.5 m
, consider the value that corresponds to
room
2
"A
=12 m
".
room
8.4
Table 2 – Minimum floor area:

indoor unit

m
(kg)
c
1.84
1.86
1.88
1.90
EHVZ04+08S18+23DA6V+9W7
Daikin Altherma 3 R F
4P618950-1 – 2020.03
(m
) (kg)
max
H=600 mm
0.138
0.276
0.414
0.553
0.691
0.829
0.907
0.970
1.028
1.084
1.137
1.187
1.236
1.283
1.328
1.371
1.413
1.454
1.494
1.533
1.571
1.608
1.644
1.679
1.714
1.748
1.781
1.814
1.846
1.877
1.909
values (i.e. when A
room
room
value from the table.
room
Minimum floor area (m²)
H=600 mm
28.81
29.44
30.08
30.72
INFORMATION
▪ For floorstanding models, the value of "Installation
height (H)" is considered 600  mm to comply to
IEC 60335-2-40:2013 A1 2016 Clause GG2.
▪ For intermediate m
two values from the table), consider the value that
corresponds to the higher m
m
=1.87  kg, consider the value that corresponds to
c
"m
=1.88 kg".
c
▪ Systems with a total refrigerant charge (m
(i.e. if the piping length is <27 m) are NOT subjected to
any requirements to the installation room.
▪ Charges >1.9 kg are NOT allowed in the unit.
8.5
Table 3 – Minimum venting
opening area for natural

ventilation: indoor unit

m
m
dm=m
–m
c
max
c
1.9
0.1
1.80
1.9
0.3
1.60
1.9
0.5
1.40
1.9
0.7
1.20
1.9
0.9
1.00
1.9
1.1
0.80
1.9
1.3
0.60
1.9
1.5
0.40
1.9
1.7
0.20
INFORMATION
▪ For floorstanding models, the value of "Installation
height (H)" is considered 600  mm to comply to
IEC 60335-2-40:2013 A1 2016 Clause GG2.
▪ For intermediate dm values (i.e. when dm is between
two dm values from the table), consider the value that
corresponds to the higher dm value from the table. If
dm=1.55  kg, consider the value that corresponds to
"dm=1.6 kg".
is
8 Technical data
values (i.e. when m
is between
c
c
value from the table. If
c
) <1.84  kg
c
(kg) Minimum venting opening area
max
2
(cm
)
H=600 mm
729
648
567
486
418
370
301
216
115
Installation manual
31