Specifications - Mitsubishi Electric PUMY-P125VMA1 Technical & Service Manual

Split-type, heat pmup air conditioners r407c outdoor unit
Table of Contents

Advertisement

4

SPECIFICATIONS

Item
Rated Cooling capacity
Rated power consumption
Operating current
Operating power factor
Starting current
Rated Heating capacity
Rated power consumption
Operating current
Operating power factor
Starting current
Rated power supply
External finish (Munsell colour-coded markings)
Dimensions H o W o D
(Note 1)
Heat exchanger type
Model
Type o quantity
Starting method
Motor output
Capacity control
Daily cooling capacity
Heater <crankcase>
Refrigerating oil (Model)
Type o quantity
Fan
Airflow
Motor output
Defrost method
Pressure gauge
High pressure protection
Compressor protection
Blower protection
Frequency converter circuit
Noise level
Weight
Refrigerant pipe size
Type o charge amount
Refrigerant
Control method
Note 1: External dimensions in parentheses indicate the dimensions of protruding parts.
Note 2: Rating conditions (JIS B 8616)
Cooling : Indoor
: D.B. 27: W.B. 19:
: Outdoor : D.B. 35: W.B. 24:
Heating : Indoor : D.B. 20:
: Outdoor : D.B. 7:
Service Ref.
Unit
kW
kW
A
%
A
kW
kW
A
%
A
mm
kW
%
Legal tons
W
L
k/min(CFM)
W
dB
kg(lbs)
Gas
[ mm
Liquid
[ mm
kg
W.B. 6:
PUMY-P125VMA
PUMY-P125VMA
28.3-27.1-26.0
28.0-26.7-25.7
Single phase 220-230-240V 50Hz
Molten-galvanized steel plate (with polyester coating), ivory white <5Y 8/1>
1280 o 1020 o 350 (+30)
Crossover fin
EEV48FAM
Fully enclosed type o 1
Frequency converter start
Cooling 27-100% Heating 25-100%
1.9 (104Hz)
1.4 (MEL32)
Propeller (direct) o 2
90(3,177)
Reverse cycle
High pressure pressure sensor (3.0MPa)
Thermal switch
Thermal switch
Overheating, Over current protection
127(280)
R407C o 8.5
Expansion valve
8
1
14.0
6.10
98
17
16.0
6.03
98
17
3.5
60 o 2
54
19.05
9.52

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pumy-p125ymaPumy-p125vmaPumy-p125yma1

Table of Contents