Mitsubishi Electric PUMY-P125VMA1 Technical & Service Manual page 71

Split-type, heat pmup air conditioners r407c outdoor unit
Table of Contents

Advertisement

9-8-5. Outdoor power circuit board
PUMY-P125VMA
PUMY-P125VMA
1
CN5
Detection of primary current
(Connect to the outdoor noise
filter circuit board (CN5))
CN6
Temperature
(Radiator panel
(THHS-B))
SC-P1
Connect to 52C
CN4
Connect to the
CN3
outdoor controller
Temperature
(Radiator panel
circuit board
(THHS-A))
(CN4)
N1
P2
P1
SC-N1
Connect to
ACTM (–)
Brief Check of POWER MODULE
W Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of POWER MODULE
1.Check of DIODE circuit
L - P1 , N - P1 , L - N1 , N - N1
2.Check of IGBT circuit
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note:The marks, L , N , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram above are not actually printed on the board.
CN2
Connect to the outdoor multi circuti board (CN2)
1-5: Power circuit board
2-5: Zero cross signal (0-5V DC)
3-4: 18V DC
CNAF
6-5: 15V DC
Connect to
7-5: 15V DC
ACTM
W
V
U
N2
N
L
}
POWER
+
MODULE
71
Transmitting
signal to the controller board (0-5V DC)
[ 5 : –
1, 2, 6, 7 : + ]
[ 4 : –
3 : + ]
TAB-U, TAB-V,
TAB-W
Connect to the
compressor (MC)
Voltage among
phases:
5V-180V AC
SC-R, SC-S
Connect to the
outdoor noise filter
circuit board
(LO, NO)
220V-240V AC
SC-P2, SC-N2
Connect to
ACTM and the
smoothing
capacitor
CNDC
300V-380V DC
Connect to the outdoor multi
circuit board (CNDC)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pumy-p125ymaPumy-p125vmaPumy-p125yma1