Mitsubishi Electric PUMY-P125VMA1 Technical & Service Manual page 16

Split-type, heat pmup air conditioners r407c outdoor unit
Table of Contents

Advertisement

5-3-2. Correcting Capacity for Changes in the Length of Refrigerant Piping
(1) During cooling, to obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and the total
in-use indoor capacity, first find the capacity ratio corresponding to the standard piping length (5m) from Figures 3
at first, and then multiply by the cooling capacity from Figure 1 to obtain the actual capacity.
(2) During heating, to find the equivalent piping length, first find the capacity ratio corresponding to standard piping length (5m)
from Figure 4, and then multiply by the heating capacity from Figure 2 to obtain the actual capacity.
(1) Cooling capacity correction factor
Figure 3. PUMY-P125VMA PUMY-P125VMA
Cooling capacity correction curve
1.0
0.9
Cooling
Capacity
(ratio)
0.9
0.7
5 10
20
piping equivaent length (m)
(2) Heating capacity correction factor
Figure 4. PUMY-P125VMA PUMY-P125VMA
Heating capacity correction curve
1.0
Heating
0.95
Capacity
(ratio)
0.9
5 10
20
piping equivaent length (m)
(3) Method for Obtaining the Equivalent Piping Length
Equivalent length for type 125 = (length of piping to farthest indoor unit) + (0.35 o number of bends in the piping) (m)
Length of piping to farthest indoor unit: type 125.....70m
5-3-3. Correction of Heating Capacity for Frost and Defrosting
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction
factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature (W.B.°C)
Correction factor
PUMY-P125YMA PUMY-P125YMA
1
63 (50%)
94 (75%)
125 (100%)
163 (130%)
30
40
50
60
70
75
PUMY-P125YMA PUMY-P125YMA
1
30
40
50
60
70 75
6
4
1.0
0.98
0.89
Total capacity for indoor unit
1
2
0
-2
0.88
0.89
16
1
-4
-6
-8
0.9
0.95
0.95
-10
0.95

Advertisement