6.9

Electrical Tests

Standards
IEC 60255 (product standard)
IEEE Std C37.90
UL 508
Additional standards are listed for the individual tests.
Installation Requirements
Overvoltage category
Degree of pollution
Protection class
Voltage-Immunity and Safety Tests
Standards
Voltage test (routine test), current measurement inputs, voltage meas-
urement inputs, relay outputs
Voltage test (routine test), auxiliary voltage, binary inputs
Voltage test (routine test), only isolated communication and time-
synchronization interfaces and analog inputs (module position E, F, M,
N, and P)
Surge immunity test (type testing), all circuits except communication
and time-synchronization interfaces and analog inputs, class III
Insulation resistance
Resistor of protective-equipotential-bonding
Voltage Immunity of the Fast Measuring-Transducer Input
Insulation (all Inputs)
Test levels (type test)
EMC Immunity Tests (Type Tests, Test under Mounting Conditions)
Standards
Electrostatic discharge test
IEC 61000-4-2
SIPROTEC 5 Compact, Hardware Description, Manual
C53000-G5340-C002-7, Edition 03.2023
Voltage immunity: DC 4.6 kV, 1 min
7.2 kV, 1.2/50 µs peak impulse
IEC 60255-1 and -26 (product standards)
EN 61000-6-2 (generic standard)
Contact discharge:
Front panel: 6 kV
Rear panel: 6 kV
Air discharge: 8 kV
Both polarities
150 pF
Ri = 330 Ω
Technical Data

6.9 Electrical Tests

III
2
1
IEC 60255-27
AC 2.5 kV
50 Hz
DC 3.5 kV
DC 700 V
5 kV (peak value)
1.2 µs/50 µs
0.5 J
3 positive and 3 negative impulses
at intervals of 1 s
> 100 MΩ @ DC 500 V
< 0.1 Ω @ DC 12 V, 30 A after
1 min.