Integrated Serial Interface - Siemens V9.50 Hardware Description

Table of Contents

Advertisement

Technical Data
6.8 Integrated Serial Interface for Short Distances
[dw_serma2_SIP5_Compact_IRIG-B, 1, en_US]
Figure 6-3
(1)
SIPROTEC 5 Compact device
(2)
SIPROTEC 5 device
(3)
IRIG-B adapter cable 7XX8310-0CG00
(4)
Time-synchronization bus cable 7XV5104-0AAxx
NOTE
i
i
The IRIG-B connection cannot be used in parallel with another serial protocol.
The IRIG-B adapter cable 7XX8310-0CG00, in particular the D-Sub connection, must be protected against
mechanical stresses (tension or vibration) by suitable relief measures. Avoid sharp bendings when
connecting the RJ45 plug.

Integrated Serial Interface

6.8.2
Description
Connector type
Baud rate
Protocol
70
Communication with IRIG B for Time Synchronization
Electrical serial asynchronous communication interface
1 x RJ45
2.4 kbit/s to 115.2 kbit/s
IEC 60870-5-103
DNP3
Modbus RTU
SUP serial
SIPROTEC 5 Compact, Hardware Description, Manual
C53000-G5340-C002-7, Edition 03.2023