Siemens V9.50 Hardware Description page 55

Table of Contents

Advertisement

[dwklest1-030211-01.tif, 1, --_--]
Figure 5-10
[dwklest2-030211-01.tif, 1, --_--]
Figure 5-11
You can connect solid conductors as well as stranded-wire conductors with ring-type lug or bootlace ferrule.
For each connection, you can install up to 2 single cables of the same type and the same cross-section.
Bridges can be used as an alternative for horizontally arranged clamping points. If bridges are used, only
ring-type lugs may be used.
The following cable cross-sections can be used for the connection of single cables:
Cable cross-section
Ferrule with plastic shroud
Stripped length
For use without ferrule
NOTE
i
i
Always guide the solid conductor or stranded-wire conductor with bootlace from the left- or right-hand side
ferrule into the terminal. Making contact from the center is not permitted.
Mechanical Requirements
The fasteners and their associated components are designed for the following mechanical requirements:
SIPROTEC 5 Compact, Hardware Description, Manual
C53000-G5340-C002-7, Edition 03.2023
Example of a Current Terminal with Connection of Cross Connectors and Single Cables
Example of a Current Terminal with Connection of 2 Single Cables
5.3 Installing Current and Voltage Terminals
AWG (American Wire Gauge) 14-10
(2.0 mm
2
to 4.0 mm
2
(0.0031 in
L = 10 mm (0.39 in) or L = 12 mm (0.47 in)
15 mm (0.59 in)
Use solid copper cables only.
Working on the Device
2
to 0.0062 in
2
))
55