2.- INSTALLATION
2.8.- ELECTRICAL CONNECTIONS
CONNECTION OF CONTROL ELEMENTS:
Air treatment unit. Example
DS
OS
AS
RS
RS HR/T
CO2
DPT
OS HR/T
AS HRT
LDRP
DADS
BAC
VOLTAGE OPERATING LIMITS: 342-462V
• 23 •
COMPONENT
Discharge sensor
Outdoor sensor
Remote ambient sensor
Remote duct sensor
Duct remote sensor for enthalpic free-cooling
CO2 Air quality probe. (Available only with enthalpic free-cooling)
Air differential pressure transducer
Outdoor sensor for enthalpic free-cooling
Remote ambient sensor for enthalpic free-cooling
Long distance connection
Smoke detector
Hot water coil
COMFORT AND SERVICE TERMINAL CONNECTION
Installation, Operation and Maintenance manual • CSC/CSH-MIL153E-1217-05/2018
STANDARD
2 x 1 mm² (shielded)
STANDARD
2 x 1 mm² (shielded)
STANDARD
2 x 1 mm² (shielded)
OPTION
2 x 1 mm² (shielded)
OPTION
6 x 1 mm² (shielded)
OPTION
4 x 1 mm² (shielded)
OPTION
3x 1 mm² (shielded)
OPTION
5 x 1 mm² (shielded)
OPTION
6 x 1 mm² (shielded)
OPTION
7 x 1,5 mm²
OPTION
5 x 1,5 mm²
OPTION
4 x 1,5 mm²