Daikin RZQ200MY1 Installation Manual page 7

Installation manual for rzq180my1 and rzq200my1
Hide thumbs Also See for RZQ200MY1:
Table of Contents

Advertisement

2. Series installation (2 or more) (note1)
• Obstacle on the suction side and both sides
(7)-2 Where there is an obstacle on the discharge side:
• No obstacle above
1. Stand-alone installation
2. Series installation (2 or more) (note1)
• Obstacle above, too
1. Stand-alone installation
2. Series installation (2 or more) (note1)
(7)-3 Where there are obstacles on both suction and discharge
sides:
Where the obstacles on the discharge side is higher than the unit:
Pattern 1
(There is no height limit for obstructions on the intake side.)
• No obstacle above
1. Stand-alone installation
L>H
2. Series installation (2 or more) (note1)
L>H
• Obstacle above, too
1. Stand-alone installation
The relations between H, A and L are as follows:
L≤H
H<L
(Note) Close the bottom of the installation frame to prevent
the discharged air from being bypassed.
2. Series installation (2 or more) (note1)
The relations between H, A and L are as follows:
L≤H
H<L
(Note1) Close the bottom of the installation frame to prevent
the discharged air from being bypassed.
(Note2) Only two units can be installed for this series.
L
A
0<L≤1/2H
750
1/2H<L≤H
1000
Set the stand as: L≤H.
L
A
0<L≤1/2H
1000
1/2H<L≤H
1250
Set the stand as: L≤H.
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzq180my1

Table of Contents