Maintenance

Cleaning
Measured value memory
Event memory
PBD-51041037
9

Diagnostics and servicing

9.1
Maintenance
If the device is used properly, no special maintenance is required in
normal operation.
The cleaning helps that the type label and markings on the instrument
are visible.
Take note of the following:
Use only cleaning agents which do not corrode the housings, type
label and seals
Use only cleaning methods corresponding to the housing protec-
tion rating
9.2

Diagnosis memory

The instrument has several memories available for diagnostic pur-
poses. The data remain there even in case of voltage interruption.
Up to 100,000 measured values can be stored in the sensor in a ring
memory. Each entry contains date/time as well as the respective
measured value. Storable values are for example:
Distance
Filling height
Percentage value
Lin. percent
Scaled
Current value
Measurement reliability
Electronics temperature
When the instrument is shipped, the measured value memory is
active and stores distance, measurement reliability and electronics
temperature every 3 minutes.
In "Extended adjustment" you can select the respective measured
values.
The requested values and recording conditions are set via a PC with
PACTware/DTM or the control system with EDD. Data are thus read
out and also reset.
Up to 500 events are automatically stored with a time stamp in the
sensor (non-deletable). Each entry contains date/time, event type,
event description and value. Event types are for example:
Modification of a parameter
Switch-on and switch-off times
Status messages (according to NE 107)
Error messages (according to NE 107)
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
SITRANS LG240 - Operating Instructions
51