SERIES 3000 MKIII TECHNICAL MANUAL

6.4 Terminal connections

All electrical connections are made at the terminal module. To access the terminal module follow the
procedure below:
1. Remove the detector's cover by unscrewing it in a counter-clockwise direction.
2. Remove the display module by pulling it firmly away from the enclosure without twisting it.
Internal Earth/
Ground Connection
Display Module
Plug in Socket
Note: Nominal tightening
torque of 6.9lb-in. to be
applied to the terminal
clamping screws.

6.5 Cable and earth / ground connection

Between the Controller and Transmitter use 2 core (plus screen 90% coverage), suitably mechanically
protected copper cable with a suitable M20 gland, or ¾ in. NPT steel conduit, with 0.5 to 2.0mm2
(equivalent approx. 20 to 14AWG) conductors. Ensure the cable gland is installed correctly and fully
tightened.
To ensure good EMC/RFI immunity bond the system to ground / earth as shown in the diagram below.
Notes:
No two 'Earth Points' should be connected via screen and / or conduit so as to avoid 'ground loops'.
(Except between the sensor and transmitter which is a digital link).
Where multiple 'Earth Points' are unavoidable (e.g. transmitter mounted on metal superstructure
which is earthed then screen and / or conduit to controller should be isolated appropriately).
' Bonded Points' (continuity of screen) may be achieved using appropriate glands / cable or conduit;
internal and external 'Earth Points' in the transmitter are provided.
Terminal
number
1
2
14
MAN0917_Issue 6_08/2015
Conduit/Cable Entry
Supplementary
External Earth/
Ground Connection
Detector
Controller
Terminal
Connection
+
+VE
-
Signal