CONNECTIONS
Power
BACnet
Supply
MS/TP
ELECTRICAL & MECHANICAL FEATURES
Plastic, type PC (UL 94 V-0)
Net dimensions (d
Enclosure
Recommended space for installation (d
Color: Light Grey. RAL 7035
Wall.
Mounting
DIN rail EN60715 TH35.
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
Terminal Wiring
1 core: 0.5mm
(for power supply and
low-voltage signals)
2 cores: 0.5mm
3 cores: not permitted
1 x Plug-in screw terminal block (3 poles)
Power
Positive, Negative, Earth
9-36 VDC / 24 VAC / 50-60 Hz / 0.140 A / 1.7 W
1 x Ethernet 10/100 Mbps RJ45
Ethernet
2 x Ethernet LED: port link and activity
1 x Serial EIA485 (Plug-in screw terminal block 3 poles)
Port
A, B, SGND (Reference ground or shield)
1500VDC isolation from other ports
Operation
0°C to +60°C
Temperature
Operational
5 to 95%, no condensation
Humidity
IP20 (IEC60529)
Protection
This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic
parts and they must be properly disposed of by following the instructions at
Rev.1.5
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply.
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within
the range admitted (check table below). The power supply can be connected to earth
but only through the negative terminal, never through the positive terminal.
Ethernet / BACnet IP
Connect the cable coming from the IP network to the connector ETH of the gateway.
Use an Ethernet CAT5 cable. If communicating through the LAN of the building,
contact the network administrator and make sure traffic on the port used is allowed
through all the LAN path (check the gateway user manual for more information). With
factory settings, after powering up the gateway, DHCP will be enabled for 30
seconds. After that time, if no IP is provided by a DHCP server, the default IP
192.168.100.246 will be set.
Port BACnet MS/TP
Connect the EIA485 bus to connectors A3 (B+), A2 (A-) and A1 (SNGD) of gateway's
Port. Respect the polarity.
Note for MS/TP port; Remember the characteristics of the standard EIA485 bus:
maximum distance of 1200 meters, maximum 32 devices connected to the bus, and
in each end of the bus it must be a termination resistor of 120 Ω.
Ethernet
BACnet IP
w
h): 93x53x58 mm
x
x
w
h): 100x60x70mm
x
x
... 2.5mm
2
2
... 1.5mm
2
2
https://intesis.com/weee-regulation
70mm (h)
60 mm (w)
URL
100 mm (d)
https://www.intesis.com
2 / 2