Page 1
CO2/Te/RH Transmitter/Controller User Manual Model : AT-VLX-A1-R1-RS Features ➢ Indoor air quality transmitter/controller ➢ Internal sensors to measure CO2 & temperature ➢ 3-color TFT screen display + 3-color alarm indication ➢ Four function keys to adjust setpoints Providing 1x analog output & 1x relay on/off output ➢...
Page 2
Accuracy <±0.5°C@25°C Electrical Specification and Functions Power supply 24VAC/VDC Power consumption 5.5 W max. ; 2.5 W avg. LCD screen 3-color TFT screen, with 4 function keys 1× analog ouotputs & 1x relay on/off output Output Analog: linear (0~10V or 4~20mA) or PID Communication interface Modbus RS485 Operation Condition...
Page 3
Fig. 2 TFT Display & Buttons The front cover contains a TFT screen and 4 function keys: SET, ▲, ▼, and Power: be used to turn on/off the transmitter/controller. When turning off, “OFF” will be displayed on the right ➢ bottom corner, and in this situation all outputs are ineffective.
Page 4
Linear Linear Linear Linear Linear Linear Linear Linear Linear Linear Linear Linear Linear Linear Linear Linear Linear Table 2 - Voltage output or current output selection via jumpers Jumpers S1~S6 on PCB Jumper SET on PCB Analog output terminals S1 connect V, S2 connect V SET connect lower two pins AN1=0~10V S1 connect V, S2 connect V...
Function Auto control Auto control Manual control Manual control ON1- decrease CO2 ON1- increase CO2 ON1- OFF ON1 -ON For example, end user may set the CO2 relay offset by Advanced Setup parameters P16. The relay 1 auto control logic is as explained below: a.
Page 6
0.0 ~ 30.0ppm 20.0 TVOC yellow to red setpoint 1 ~ 4 (see table 4) The relay mode for CO2 1 ~ 4 (see table 5) The relay mode for Temp 1 ~ 4 (see table 6) The relay mode for Humi 1 ~ 4 (see table 7) The relay mode for TVOC 1 ~ 5000ppm...
Page 7
CO2 PID period setpoint 0.1 ~ 10000.0 CO2 PID-P setpoint -10000 ~ 10000 -2.0 CO2 PID-I setpoint 0.0 ~ 10000.0 10.0 CO2 PID-D setpoint 0.0 ~ 10000.0 10.0 Temp PID period setpoint 0.1 ~ 10000.0 Temp PID-P setpoint -10000 ~ 10000 Temp PID-I setpoint 0.0 ~ 10000.0 10.0...
Page 8
TVOC PID self-tuning 1- Run TVOC control PID self-tuning 0- stop PID self-tuning Power on again 1- turn off 2-turn on after power up again 3- hold the mode before the power failure Temperature unit 1- Degree Celsius; 2- Fahrenheit CO2 ABC Logic ABC Logic ON;...
Page 10
Humi. UINT16 1~100 => 1~100 RH% Measurement x 1 times TVOC UINT16 0~30 => 0~30ppm measurement x 1 times Co2 Measurement UINT16 0~5000 => 0~5000 ppm Temp. INT16 -200~600 =>-20.0~60.0℃/ Measurement -400~1400=>-40.0~140.0 ℉ x 10 times Humi. UINT16 1~1000 => 0.1~100.0 RH% Measurement x 10 times TVOC...
Page 11
choice Temperature unit UINT16 1-Degree Celsius; P-66 selection 2-Fahrenheit AN1 AN2 AN3 UINT16 0~15 Table 3 PID or Linear output choice Co2 setpoint for 3/16 Float 0~5000ppm User “Co2 relay1 and Big-endian setpoint” AN1(0~10V/4~20 mA) PID Temp setpoint for 3/16 Float 21.0 User “Temp...
Page 12
AN1(0~10V/4~20 mA) PID Temp setpoint for INT16 -200~600 => -20.0~60.0℃ User“Temp relay2 and setpoint” AN2(0~10V/4~20 mA) PID x 10 times Humi setpoint for UINT16 0~1000 => 0.0~100.0%RH User“Humi relay3 and setpoint” AN3(0~10V/4~20 mA) PID x 10 times TVOC setpoint for UINT16 0~300 =>...
Page 13
AN1 CO2 linear 3/16 Float 0~5000ppm 5000 P-23 max value Big-endian 0~10.000v 10.000 P-24 AN1 CO2 linear 3/16 Float max volt Big-endian AN2 Temp linear 3/16 Float P-25 -20.0~60.0℃ -20.0 Big-endian AN2 Temp linear 3/16 Float 0~10.000v 0.000 P-26 Big-endian AN2 Temp linear 3/16 Float...
Page 14
2-auto control relay ON3-> humidification 3-hand control relay ON3-> 4-hand control relay ON3-> P-15 the relay mode for UINT16 1-auto control relay ON3-> TVOC reduce TVOC 2-auto control relay ON3-> increase TVOC 3-hand control relay ON3-> 4-hand control relay ON3-> CO2 offset for 3/16 Float...
Need help?
Do you have a question about the AT-VLX-A1-R1-RS and is the answer not in the manual?
Questions and answers