Daikin Altherma 3 H HT ETSX16E7 Installer's Reference Manual page 301

Table of Contents

Advertisement

12/19
Field settings table
Breadcrumb
Setting name
9.I
[1-0B]
What is the desired delta T in heating for the main zone?
9.I
[1-0C]
What is the desired delta T in heating for the additional zone?
What is the desired delta T in cooling for the main zone?
9.I
[1-0D]
9.I
[1-0E]
What is the desired delta T in cooling for the additional zone?
9.I
[2-00]
When should the disinfection function be executed?
9.I
[2-01]
Should the disinfection function be executed?
9.I
[2-02]
When should the disinfection function start?
9.I
[2-03]
What is the disinfection target temperature?
9.I
[2-04]
How long must the tank temperature be maintained?
9.I
[2-05]
Room antifrost temperature
9.I
[2-06]
Room frost protection
9.I
[2-09]
Adjust the offset on the measured room temperature
9.I
[2-0A]
Adjust the offset on the measured room temperature
9.I
[2-0B]
What is the required offset on the measured outdoor temp.?
9.I
[2-0C]
What emitter type is connected to the main LWT zone?
9.I
[2-0D]
What emitter type is connected to the additional LWT zone?
9.I
[2-0E]
What is the maximum allowed current over the heatpump ?
9.I
[3-00]
Is auto restart of the unit allowed?
9.I
[3-01]
--
9.I
[3-02]
--
9.I
[3-03]
--
9.I
[3-04]
--
9.I
[3-05]
--
9.I
[3-06]
What is the maximum desired room temperature in heating?
9.I
[3-07]
What is the mimimum desired room temperature in heating?
9.I
[3-08]
What is the maximum desired room temperature in cooling?
9.I
[3-09]
What is the minimum desired room temperature in cooling?
9.I
[3-0A]
--
9.I
[3-0B]
--
9.I
[3-0C]
--
4P681797-1B - 2022.09
Range, step
Default value
R/W(*10)
3~10°C, step: 1°C (*9)
[2-0D]=2
3~12°C, step: 1°C (*10)
R/O (*9)
[2-0C] ≠ 2 (Radiator)
5°C
[2-0C] = 2 (Radiator)
10°C
R/W(*10)
3~10°C, step: 1°C (*9)
[2-0D]=2
3~12°C, step: 1°C (*10)
R/O (*9)
[2-0C] ≠ 2 (Radiator)
5°C
[2-0C] = 2 (Radiator)
10°C
R/W
3~10°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0: No
1: Yes
R/W
0~23 hour, step: 1 hour
1
R/W
60°C
60°C
R/W
40~60 min, step: 5 min
40 min
R/W
4~16°C, step: 1°C
8°C
R/W
0: No
1: Yes
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
20~50 A, step: 1 A
50 A
R/W
0: manual
1: automatic
R/W
0
R/W
1
R/W
4
R/W
2
R/W
1
R/W
18~30°C, step: 1°C
30°C
R/W
12~18°C, step: 1°C
12°C
R/W
25~35°C, step: 1°C
35°C
R/W
15~25°C, step: 1°C
15°C
0
1
1
(*1) *X*_(*2) *H*_(*3) *B*_(*4) *EKECBUA*3V_
(*5) *EKECBUA*6V_(*6) *EKECBUA*9W_(*7) BUH less_
(*8) 300L tank_(*9) E_(*10) E7