The gas supply must be capable of handling the
entire gas load required at the location. Gas line
sizing is based on gas type, the pressure drop
in the system, the gas pressure supplied, and
gas line type. For gas pipe sizing in the United
States, refer to the National Fuel Gas Code,
NFPA 54, and/or CSA B149.1.
The below information is provided as an exam-
ple. The appropriate table from the applicable
code must be used.
1. For some tables, you will need to determine
the cubic feet per hour of gas required by
dividing the gas input by the heating value
of the gas (available from the local gas
company). The gas input needs to include
all gas products at the location and the
maximum BTU usage at full load when all
gas products are in use.
2. Use the table for your gas type and pipe
type to find the pipe size required. The pipe
size must be able to provide the required
cubic feet per hour of gas or the required
BTU/hour.
Example:
The heating value of natural gas for your loca-
3
tion is 1000 BTU/FT
. The gas input of the
CHS19980REC is 199,000 BTU/HR. Additional
appliances at the location require 65,000 BTU/
hr. Therefore the cubic feet per hour = (199,000
+ 65,000) / 1000 = 264 FT
length is 10 feet then the 3/4 inch pipe size is
capable of supplying 264 FT
Gas Input of all gas products (BTU/HR)
(CFH) =
Heating Value of Gas (BTU/FT
28
3
/HR. If the pipe
3
/HR of natural gas.
3
)
Demand Duo™ R-Series (REC) Installation and Operation Manual
Table 7: Pipe Sizing Table - Natural Gas
Pipe Sizing Table - Natural Gas
Schedule 40 Metallic Pipe
Inlet Pressure:
less than 2 psi (55 inches W.C.)
Pressure Drop: 0.3 inches W.C.
Specific Gravity: 0.60
Cubic Feet per Hour (CFH)
Pipe Size (inches)
Length
3/4
10
273
20
188
30
151
40
129
50
114
60
104
70
95
80
89
90
83
100
79
Table 8: Pipe Sizing Table - Propane Gas
Pipe Sizing Table - Propane Gas
Schedule 40 Metallic Pipe
Inlet Pressure:
11.0 inches W.C.
Pressure Drop: 0.5 inches W.C.
Specific Gravity: 1.50
Capacity in Thousands of BTU per Hour
Pipe Size (inches)
Length
1/2
3/4
10
291
608
20
200
418
30
160
336
40
137
287
50
122
255
60
110
231
80
101
212
100
94
197
1
1 1/4
1 1/2
514
1,060
1,580
353
726
1,090
284
583
873
243
499
747
215
442
662
195
400
600
179
368
552
167
343
514
157
322
482
148
304
455
1
1 1/4
1,150
2,350
787
1,620
632
1,300
541
1,110
480
985
434
892
400
821
372
763