GRUNDFOS INSTRUCTIONS LC 232 Single pump unit Installation and operating instructions LC 232 single pump unit Installation and operating instructions Other languages http://net.grundfos.com/qr/i/99918634...
Page 3
LC 232 English (GB) Installation and operating instructions ............5 Български...
2.2.5 Installing a communication interface module 2.3.4 Connecting a level sensor Related information 3.6 Configuring the IO terminals using Grundfos GO Remote 2.3.3 Connecting the pump supply and power supply 2.2.4 Disconnecting the front cover 2.2.2 Mounting the rubber insert...
The module is Changes or modifications not expressly approved by optional and is not delivered with the product. See the installation Grundfos may void the user's authority to operate the and operating instruction for the module regarding electrical equipment.
Page 8
PTC wire, a moisture sensor wire and a supply cannot be switched on accidentally. common wire. Connect only the PTC wire and the moisture sensor wire. The common wire must be isolated.In Grundfos GO ‐ Remember to indicate where the main switch is...
Page 9
Remote. You can either connect an analog level sensor, such as a pressure Go to Settings > LC 232 IO terminals > Relay output > Function. sensor, or digital level sensors, such as float switches. Default settings of the terminal blocks 1.
The app is free of charge and available for iOS and Android devices. 1. Open Grundfos GO Remote on your device. Make sure that Bluetooth is enabled. Your device must be within reach of the product to establish Bluetooth connection.
1. Press and hold the connect button on the operating panel for 15 • dewatering in groundwater supply seconds. Wait for the blue LED to switch off. Grundfos GO Remote is no longer connected to the product. • filling a tank. The product can be used for the following applications: Related information •...
The liquid is pumped into a second tank where the level sensors are installed. Connect to Grundfos GO Remote to see which options are The pump starts to fill the second tank when Start level P1 is available for the input and output terminals.
4.7 Supported communication interface modules and Connect button: protocols • Press this button to connect the control unit The following Grundfos communication interface modules can be to Grundfos GO Remote via Bluetooth. added to the product. Reset button: • Press this button during startup to reset...
Off: The pump has been switched off 6.4 Setting the stop level manually. Status Settings Assist 6.4.1 Setting the stop level with Grundfos GO Remote • Auto: The pump is running automatically based on settings. The settings apply to analog sensors. For digital sensors, the...
The specific level depends on the installed pump type. See the installation and operating You can set a time in Grundfos GO Remote in order to get a instructions for the product. reminder that the pump needs service when the time comes.
6.15.4 Setting the motor protection with Grundfos GO Remote • Return to 6.15.4 Setting the motor protection with Grundfos GO Remote Here you select whether the pump must return to automatic operating mode or stop when the manual start ends and You can set the current, temperature and moisture protection via a Automatic return has been enabled.
Page 17
1. Go to Settings > Motor protection pump 1. the control unit. Maximum number of blocked motor restart can be set from 1 to 3 via Grundfos GO Remote. Tripped by the CCP- 2. Follow the on-screen instructions to set the nominal pump curve.
GENIbus, the Grundfos Electronics Network Intercommunications 2. Select one of the following: bus, is a fieldbus developed by Grundfos to meet the need for data transfer in all typical Grundfos motor or pump applications. The control unit does not reset...
The alarm symbol on the display turns red and the pump stops. 4. Remove the screws that holds the module. • Alarm code Power phase missing is displayed in Grundfos GO 5. Remove the module from the control unit. Remote.
The alarm symbol on the display turns red and the pump stops. Related information • Alarm code Too many motor restarts is displayed in Grundfos 3.6 Configuring the IO terminals using Grundfos GO Remote GO Remote. 8.8 Code 26 (Contactor shorted)
The alarm symbol on the display turns red and the pump stops. • The warning symbol on the display turns yellow and the pump's • Alarm code Dry run is displayed in Grundfos GO Remote. operating mode is unchanged. • Warning code Memory storage media faulty is displayed in...
The alarm symbol on the display turns red and the pump stops. • Alarm code 205 is shown on the display. • Alarm code Signal fault is displayed in Grundfos GO Remote. • The alarm symbol on the display turns red and the pump stops. Cause Remedy •...
Model temperature combination Pump cable 16-21 mm (0.6" - 0.83"), with optional metal cable gland 99920061 LC 232 1x 1-12 12 A and 45 °C (113 °F) DOL 3x460 PI CE Sensor cable 5-8 mm (0.19" - 0.3") Mains input terminal...
This product or parts of it must be disposed of in an environmentally sound way. 1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop. 3. Dispose of the waste battery through the national collective schemes.