8.2.4

Safety components

The safety components should be replaced at the end of their life
cycle indicated in Tab. O.
The specified life cycles do not refer to the warranty terms indi-
cated in the delivery or payment conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor
(electronic cam) (if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Hoses (if present)
Fan impeller
Maintenance
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000
pressurised cycles
10 years or 500,000 start-ups
Tab. O
35