Calibration Of Thermal Relay; Current To The Uv Photocell - Riello Bio RLS 68/M Installation, Use And Maintenance Instructions

Dual fuel gas oil/ gas burner
Table of Contents

Advertisement

6.3

Calibration of thermal relay

This is required to avoid motor burn-out in the event of a signifi-
cant increase in power absorption caused by a missing phase.
If the motor is star-powered, 400V, the cursor should be po-
sitioned to "MIN".
If the motor is delta-powered, 230V, the cursor should be po-
sitioned to "MAX".
Even if the scale of the thermal cut-out does not include rated mo-
tor absorption at 400V, protection is still ensured in any case.
D867
6.4

Current to the UV photocell

Min value for a good work: 70 µA.
If the value is lower, it can depend on:
exhausted photocell;
low current (lower than 187 V);
bad regulation of the burner.
In order to measure the current, use a microammeter of 100 A
c.c., connected to the photocell, as in the scheme, with a capac-
itor of 100 F - 1V c.c. at the same level of the instrument.
See Fig. 31.
D1143
20034985
Electrical system
WARNING
Fig. 30
Fig. 31
26
GB
Do not invert the neutral with the phase wire
in the electricity supply line. Any inversion
would cause a lockout due to firing failure.
Only use original spare parts to replace the
components.