System Shutdown; Automatic System Standby And Restart - SPX MARLEY WaterGard WG002 User Manual

Table of Contents

Advertisement

operation

System Shutdown

Less than 30 days. Press and hold the SYSTEM ON/OFF key (the display
will show POWER OFF).
More than 30 days. Drain the system of as much water as possible by break-
ing unions or removing tubes. On startup, follow Startup procedure.

Automatic System Standby and Restart

System will automatically go into standby during the following conditions:
• Collection Basin full
• Low inlet pressure
Once the collection basin water level drops below its actuation point
WaterGard will restart.
Bypass
System will automatically go into bypass during the following conditions:
• When WaterGard is in a shutdown condition
– Low inlet pressure and has faulted 5 times or more
– Pretreat fault has been active for more than 2 seconds
• When the LLC low level alarm has been activated.
11