Summary of Contents for SPX MARLEY WaterGard WG002
Page 1
u s e r m a n u a l ™ WaterGard model WG002-WG004-WG007-WG009 I N STA L L AT I O N - O P E R AT I O N - M A I N T E N A N C E 1 0 0 0 0 0 2 2 0 0 2 I S S U E D 5 /20 2 3 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT.
contents This manual contains vital information for the proper installation Note and operation of the Marley WaterGard system. Carefully read the manual before installation or operation and follow all instructions. Save this manual for future reference. Technical Information ....................3 System Requirements ....................4 Schematics and Components .................5 Rigging ..........................7 Physical System Requirements ................7...
Any such deviation, change or modification shall be the responsibility of the party or parties making such deviation, change or modification. SPX Cooling Tech expressly disclaims all liability for any such deviation, change or modification. The equipment shall be warranted in accordance with the applicable SPX Cooling Tech Certification of Limited Warranty.
Feedwater Requirements Table 3. This can either be done by purchas- ing a carbon tank through SPX Cooling or using liquid chemical chlorine destruct from a chemical water treater.
installation Rigging The WaterGard unit should be lifted and moved by a forklift. If the WaterGard unit is lifted by a crane it should be lifted from the bottom using a platform. The unit should be secure to the platform using the anchor locations. A test lift should be done in order to determine the weight centerline.
installation Electrical Requirements WaterGard’s provided cord serves as the ground. Conduit and water Warning pipes are NOT an acceptable ground. • All wiring must be properly sized, rated, and connected in accordance with local, state, and national electrical codes. The system is pre-wired and tested at the factory.
operation Startup and Operation WaterGard membranes cannot be used immediately, they must Note be filled with feed water and allowed to soak for a minimum of 30 minutes, see step 10. 1. Connect the carbon filter (if present) to your potable water supply. The carbon filter will need to be flushed for 30 minutes before being piped into WaterGard.
Page 10
operation 12. Once the pump has started, membrane inlet (pump) pressure should never exceed 135 psi. Use the valve on the discharge side of the pump to adjust the pressure to 105 psi. If pressures over 135 psi are observed it could be an indication of membrane fouling.
operation System Shutdown Less than 30 days. Press and hold the SYSTEM ON/OFF key (the display will show POWER OFF). More than 30 days. Drain the system of as much water as possible by break- ing unions or removing tubes. On startup, follow Startup procedure. Automatic System Standby and Restart System will automatically go into standby during the following conditions: •...
operation Operating Status Messages The main operating status of the unit is shown on the top line of the display: POWER OFF: The unit is off. RO RUNNING: WaterGard unit is operating. RO STARTING: WaterGard unit is starting up. TANK FULL: The unit is shut down due to a collection basin full condition. PRETREAT: The Unit is shut down due to a pretreat lockout condition.
Page 14
operation Warning Messages—Warning messages are also shown on the second line. If any warnings are active, the active warnings will alternate with normal dis- plays for the bottom line. Tank Full Operation—The unit can be operated with either the Marley LLC or Marley LLC+u water level controls.
operation acceptance quality range. Alarm Output—The board Divert/Alarm has been programmed to operate as Standard Setpoints on page 20 shows, the relay will energize whenever a shutdown condition occurs. The relay will remain energized if the shutdown condition is active. S1 should be left as a powered output for the bypass feature to function.
Page 16
operation Permeate Conductivity Fault: Permeate conductivity is higher than the alarm setpoint Line 1—Service Fault Line 2—Permeate TDS xxx ppm or Permeate Cond xxx µS Line 3—Alarm SP xxx ppm or Alarm SP xxx µS Line 4—To Reset Push OFF/ON Conductivity Probe Error messages: Line 2 —Over-range Measurement is out of range for the circuit, probe may also be shorted...
operation Internal excitation voltage too low to make valid measurement Controller Adjustment ➠ RO Presets Program 1 RO Presets Program 1 VALUES 1, 2, 3, 4 ^v for Other Menus ^v to change setting Manual=Edit Sys=Exit Manual=Save Sys=Undo Save- Return to RO Display Temperature Mode: °C Temperature Mode: °C VALUES...
operation With the system ON, press and hold the UP and DOWN arrows and then press System On/Off. Figure 7 shows the settings that can be changed at the controller. WaterGard Presets Program—Change program to number of program desired. Setpoints are shown in Standard Setpoints on page 20. Temperature Mode—Select temperature unit desired.
Page 19
operation 5. Exit and save the calibration. 6. The same procedure applies to the Feed Probe calibration. The probe calibration must be performed using solutions with con- Note ductivity of less than 900 ppm or μS. The conductivity calibration circuit will behave erratically if you attempt to calibrate using a higher value.
operation Standard Setpoints Parameter Value Program 1 Program 2 Program 3 Program 4 Timed Manual Run Minutes Collection Basin Level Switch delay Seconds (actuation and de actuation) Pressure Switch delay Seconds (actuation and de actuation) Pretreat Switch delay Seconds (actuation and de actuation) Pump start delay Seconds Pump start retry interval...
troubleshooting Display Adjustment—Change LCD brightness and LCD contrast to adjust for the application’s best viewing experience. Only those persons who have read the complete user manual or who Caution Trouble Cause Remedy WaterGard not supplied power Reestablish power. WaterGard will Circuit breaker tripped Reset the breaker.
Page 22
Care should be taken when troubleshooting any of the input power or output circuits. When disconnecting or connecting any board or accessory, verify that power is off. Before contacting SPX Cooling for technical help, verify the programming Trouble Cause Remedy...
maintenance of all setpoints, check the display and the status of all lights and indicators. The more information available when you contact us, the easier it will be to determine the source of the problem. Servicing If any component of the water treatment system is changed or re- Note placed, the user should conduct appropriate tests to ensure that the revised system meets all standards to which it was initially tested.
Page 24
maintenance Typical Service Intervals Task Frequency Estimated Replacement Time Yearly or as quality degrades to be more than 35% of Membrane replacement 15 minutes per membrane incoming conductivity, which- ever comes first. Quarterly or when ∆P across Sediment filter replacement 5 minutes Sediment filter is ≥10 psi.
Page 25
maintenance 3. Remove end cap. It may be tightly sealed and require some force to re- move. Use a flat object and carefully pry up around the cap. For models where the cap has a crossover tube to another membrane, it is best to remove both end caps at the same time.
Page 26
maintenance feels like you are forcing the housing into place, the filter is not vertical and seating in the top cap. 6. Turn feedwater back on, and return to normal operation Carbon Filter Replacement 1. Turn off the feedwater supply to the system by shutting off the inlet and Figure 10 outlet valves 2.
8. Turn feedwater back on flush carbon for 30 minutes, see Item 1 in Startup and Operation on page 9 more info. 9. Return to normal operation Part Number Description Contact your Marley Sales Representative or SPX Cooling for pricing. WaterGard Membrane Note 2800054 Replacement Membrane 4" x 40"...
Need help?
Do you have a question about the MARLEY WaterGard WG002 and is the answer not in the manual?
Questions and answers