How to obtain the cooling and heating capacity
Example : The net cooling capacity of the model FDT200VSADVH with the air flow "P-Hi", the piping length of 15m, the outdoor
unit located 5m lower than the indoor unit, indoor wet-bulbtemperature at 19.0℃ and outdoor dry-bulb temperature 35℃ is
Net cooling capacity =
Net cooling total capacity
of FDT200VSADVH
(Outdoor temp. : 35℃DB
Indoor temp. : 19℃WB)
shown in 2.8.1
×
×
19.0
1.00
Air flow : P-Hi
shown in 2.8.2
Piping length :15m
(Gas pipe size is
shown in 2.8.3
303
-
.
×
0.991
0.99
= . 18.6kW
Height diff. : 5m
(Outdoor unit : below)
shown in 2.8.4
φ
22.22)
-