8.2.5 SERVICE SWITCH
The service switch is not part of the unit delivered without the I&C system.
service switch is a part of the control box - see. picture.
8.2.6 SERVICE ACCESSES
All service accesses are from the front (service) side of the unit.
8.2.7 PERIODIC INSPECTIONS
Perform periodic inspections at least once a year as part of a summer service inspection. It is optimal to carry out inspections twice a year,
usually before and after the end of the winter season.
During the regular service inspection it is necessary in particular:
–
Perform regular inspection and cleaning of the heat exchange surfaces of the exchangers
–
Clean or replace filter inserts in air filters
–
check the condition of the damping inserts, especially their tightness, and replace them in time
–
Perform inspections and checks of the function of electrical components (contactors contacts, tightening of terminals, condition of
insulation...)
–
Check the hinges and supports of the device
–
check the siphons for condensate drainage, especially their permeability and tightness, especially the tightness of the attachment
to the unit and the tightness of the ball seating (in the case of overpressure siphons, fill the siphons with water)
–
Carry out regular inspections of those facilities for which the applicable laws, decrees, standards and rules so require
–
Keep proper records and monitoring of the outcome of inspections and revisions and monitor the implementation of the measures
taken
8.2.8 SPARE PARTS
Warranty, post-warranty service and spare parts can be ordered from S&P UK Ventilation Systems Ltd.
to
trained authorized service companies. Their list is at www.solerplau.co.uk. Contact details for authorized service are indicated on the
yellow labels on each unit.
AUTHORIZED SERVICE
9. DECOMMISSIONING AND RECYCLING
EU law and our responsibility to future generations oblige us to recycle used materials; do not forget to dispose of all unwanted
packaging materials at the appropriate recycling points and dispose of obsolete equipment at the nearest waste disposal site.
In case of any questions regarding our products, please contact any branch of S&P UK Ventilation Systems Ltd.
To find
your nearest dealer, visit our website www.solerplau.co.uk.