Installation; Place Of Installation; Distances From Building Structures (Service Space) - S&P DUOVENT MODULAR DV Instruction Manual

Ventilation units with heat recuperation
Table of Contents

Advertisement

The units must be stored in dry and dust-free areas where the ambient temperature does not fall below + 5 °C. The unit must be protected during
storage against mechanical damage, dirt and corrosion caused by permanent condensation of water vapour on the surface of the unit. During
storage, it is necessary to protect the units against snow, rain and other weather conditions (store in a covered warehouse).
When accepting the unit, it is necessary to check whether the product was delivered in the agreed design and extent, whether it was not
damaged during transport, whether there is no condensed water under the plastic wrap (if there is moisture under the packaging, unpack the
unit and dry in a covered dry place) . In case of damage during transport, the transferee must record the extent of damage in the Delivery Note,
obtain and send photo documentation to S&P UK Ventilation Systems Ltd. Failure to comply with this procedure exposes the transferee to the
risk of rejection of the complaint by S&P UK Ventilation Systems Ltd.

5. INSTALLATION

The unit can only be installed by a professional installation company authorized in accordance with the Trade Licensing Act.

5.1 PLACE OF INSTALLATION

The unit can only be installed in accordance with the "Environmental Protocol", in which the characteristics of all devices that can be placed in
this space are clearly defined, and it is not possible to place devices that would affect these conditions in any way. The unit has a limited load
capacity and is certainly not intended for storing and depositing any materials, especially objects of considerable weight. This could deform the
housing of the unit or severely damage it. These damages are not covered by the warranty. After connecting the unit to the HVAC piping, it is
necessary to check the insulation of the HVAC piping in parts with a risk of condensation. Condensate formed in the air duct can, in
unfavourable conditions, spill into the interior of the unit, where it is not separated and may flow out of the unit. The result of this process can be
damage to adjacent building structures.

5.1.1 DISTANCES FROM BUILDING STRUCTURES (SERVICE SPACE)

Observe the minimum recommended distances from all obstacles to ensure easy maintenance and operation of the unit. If the unit is fitted with
®
Digireg
control system, it is necessary to ensure free space from the system distribution box of at least 800 mm and the space for free opening
of the doors. It is also necessary to ensure distances on the side of connecting the air duct to the unit. All media connections and MaR, or other
constructions, must not prevent the full opening of all openings (doors) used for operation and maintenance of the unit. Unless otherwise stated
in the order, the control system switchboard will always be located on the operating side of the unit (see figures below). The atypical location of
the switchboard must be specified in the order. There must be free access to the distribution box; the quality of access must not be impaired
by small or protruding objects in the way, slippery floors, etc. The distribution box must not be surrounded in such a way as to impair the transfer
of heat to the surrounding area. If it is allowed to store and store objects in the vicinity of the switchboard, a minimum space must be marked,
which must remain free. It is not allowed to place any objects on the distribution box.
Minimum service space of DUOVENT
Size
DV 8500
DV 10100
DV 12000
DV 14500
®
MODULAR DV:
A [mm]
1620
1777
1934
2091
L
I&C control box – Digireg
®
Ventilation units with heat recuperation
®
DUOVENT
B [mm]
L [mm]
1620
3289
1777
3525
1934
3604
2091
3996
A
MODULAR DV/RV
S [mm]
1700
1800
2000
2150
S