Siemens RWF50.3 User Manual page 40

Compact universal controllers
Table of Contents

Advertisement

Display of controller
parameters
Parameter
Proportional band ¹
Derivative time
Integral action time
Dead band (neutral
zone) ¹
Controlling element
running time
Switch-on threshold
Heating controller ¹
Switch-off threshold
stage II
Heating controller ¹
Switch-off threshold
Heating controller ¹
Switch-on threshold
Cooling controller ¹
Switch-off threshold
stage II
Cooling controller ¹
Switch-off threshold
Cooling controller ¹
Response threshold
40/64
Building Technologies Division
Infrastructure & Cities Sector
The parameters are shown on the lower setpoint display (green) and their values on the
upper/actual value display (red).
Display
Value range
1...9999 digit
Pb1
0...9999 s
dt
0...9999 s
rt
0.0...999.9 digit
db
10...3000 s
tt
-1999...0.0 digit
HYS1
0.0...HYS3 digit
HYS2
0.0...9999 digit
HYS3
0.0...9999 digit
HYS4
HYS6...0.0 digit
HYS5
-1999...0.0 digit
HYS6
0.0...999.9
q
¹
Setting of decimal place has an impact on this parameter
Note!
When using the RWF50... as a modulating controller only, or as a modulating
controller without the burner release function (1P, 1N), parameter HYS1 must be set to
0 and parameters HYS2 and HYS3 must be set to their maximum values.
Otherwise, for example, when using default parameter HYS1 (factory setting -5), the 3-
position controller is only released when the control deviation reaches -5 K.
User Manual RWF50...
7 Parameterization PArA
Factory
Remarks
setting
10
Influences the controller's P-action
Influences the controller's D-action
80
With dt = 0, the controller has no D-action
Influences the controller's I-action
350
With rt = 0, the controller has no I-action
For 3-position output
Y
100%
1
-100%
Running time of the positioning valve for use
15
with modulating controllers
Reference!
-5
See chapter 5.2 High-fire operation
Reference!
3
See chapter 5.2 High-fire operation
Reference!
5
See chapter 5.2 High-fire operation
Reference!
5
See chapter 5.2 High-fire operation
Reference!
-3
See chapter 5.2 High-fire operation
Reference!
-5
See chapter 5.2 High-fire operation
Reference!
0
See chapter 5.5 Response threshold
(q)
db
W
X
7866d13/0911
CC1U7866en
25.07.2014