If your computer room uses floor cutouts to route power and data cables, position the cutouts
toward the center of the rack. If this is not possible, position the cutouts off-center from the
rack as long as the cutout is within the allowable range and allows smooth routing and
entrance of cables. Check the relationship between the position of the cutout and the cable
openings on the rack.
Floor load rating
The floor space at the installation site must support the combined weight of all associated
component and equipment. The maximum load rating is 709 kg.
Installing anti-tilt bracket for Universal V3 Rack
The anti-tilt bracked for the Hitachi Universal V3 Rack must be anchored to a rigid floor
capable of holding a minimum of 154 lbs (79 kg).
Before you begin
To install the anti-tilt bracket, you will need the following tools and components:
T25 screwdriver
■
Customer supplied M10 or 3/8" screw capable of holding a minumum 154 lbs (79 kg)
■
Procedure
1. Adjust the four retractable feet so the rack is level with the ground.
2. Attach two anti-tilt brackets to the feet on the back of the rack.
Hitachi Virtual Storage Platform E990 Hardware Reference Guide
Chapter 5: Site preparation
Floor load rating
46