Page 1
Technical manual Ductimax Duct units M edi um static pressure 2-8 k W Supervision 2 pipes systems 4 pipes systems Centrifugal fan Ducted GARDA PLUS » Multi speed motor » Heat exchanger up to 4 rows » Water connections » ABS centrifugal fans »...
Page 2
Dear Customer, Thank you for placing your trust in one of the products of Galletti S.p.a This product is the result of our work and our commitment to design, research, and production and has been made from the finest materials, employing state-of-the-art components and production technology.
Heat exchanger can be optimized for centralized applications The action of the G3 air filter can be combined with an air ioni- such as district cooling. DUCTIMAX was designed to ceiling hori- sation system. zontal installation.
Ū 20-14 = 6 °C in order to avoid condensation on a fancoil equipped with a valve. Ū 20-12 = 8 °C If the valve kit accessory can not be installed. DUCTIMAX TECHNICAL MANUAL...
Freezing Capacity Pressure drop % Glycol by weight temperature (°C) adjustment adjustment 1,00 1,00 0,97 1,05 0,92 1,10 0,87 1,15 0,82 1,20 ASSEMBLY OF UNITS Mounting the unit that the unit is properly inclined so as to facilitate condesate Insert the vibration dampers provided in the 4 slots indicated for drainage (figure 3.2 ...
Air inlet and outlet plenum box Air Inlet plenum box with double row grille Air Inlet plenum box with double row grille 300 x 600 mm and filter G2 Insulated air outlet plenum box with grille Accessories Condensate drainage pump kit DUCTIMAX TECHNICAL MANUAL...
PERFORMANCES Galletti has developed on its www.galletti.com web-area the new ON-LINE integrated platform for product selection, configuration and the making of the economic offer. The software, whose use is easy and intuitive, allows the identification of the desired products by calculating their performances based on real working conditions and their configuration helping the user in choosing options and accessories.
SOUND POWER LEVELS FOR 2-PIPES OCTAVE BAND 1000 2000 4000 8000 1000 2000 4000 8000 125 Hz 250 Hz 500 Hz Lw OUT 125 Hz 250 Hz 500 Hz IN+R Model dB(A) dB(A) 54,2 51,9 48,2 43,8 40,2 34,2 25,5 53,2 50,9 47,2...
Page 16
39,2 40,5 Data referring to filter G3 units at PU = 0 Pa - For all operating points and work limits not present in the upper table, refer to the Galletti S.p.A. selection program LW _out: Octave sound power level - outlet...
10 SOUND POWER LEVELS FOR OCTAVE BAND 4 PIPE SYSTEMS AND 1 ROW 1000 2000 4000 8000 1000 2000 4000 8000 125 Hz 250 Hz 500 Hz Lw OUT 125 Hz 250 Hz 500 Hz IN+R Model dB(A) dB(A) 54,2 51,9 48,2 43,8...
Page 18
39,2 40,5 Data referring to filter G3 units at PU = 0 Pa - For all operating points and work limits not present in the upper table, refer to the Galletti S.p.A. selection program LW _out: Octave sound power level - outlet...
11 OVERALL DIMENSIONS » Ductimax 1 - 4 LEGEND Water connections standard heat exchanger 1/2" female gas Water connections additional heat exchanger 1/2" female gas Condensate discharge diameter ø 17 DUCTIMAX UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 20
» Ductimax 5 - 6 1096 1066 1177 1123 LEGEND Standard heat exchanger water connections 3/4” gas female Water connections additional heat exchanger 1/2" female gas Condensate discharge diameter ø 17 DUCTIMAX TECHNICAL MANUAL...
DUCTIMAX 13-14 6-speed motor (+ EVO/ MYCOMFORT / TED) DUCTIMAX 23-54 7-speed motor (+ EVO/ MYCOMFORT / TED) DUCTIMAX 63-64 Motor 4 speed (+ EVO/ MYCOMFORT / TED) NOTE: The electric wires (power and control circuits) must be pulled in through the gland on the side of the electric box where the plumbing connections are located and then con- nected to the terminals.
ATTENZIONE: Il cavo COMUNE del motore é quello di colore » DM1- Wiring diagram Phase Blue Brown Ground Neutre Grey Fuse (not provided) Green Circuit breaker (not supplied) Yellow ..Wirings made by supplier Rosso White GYNE Yellow/green = ground (PE) Nero DUCTIMAX TECHNICAL MANUAL...
Page 23
» DM2 - DM 5 Wiring diagram Phase Blue Ground Brown Neutre Grey Fuse (not provided) Green Circuit breaker (not supplied) Yellow ..Wirings made by supplier Rosso GYNE White Yellow/green = ground (PE) Nero » DM6 - Wiring diagram Phase Blue Ground...
Page 24
» MCB V DM 1 WH(M): White = Neutral BK(M): Black BU(M): Blue GY(M): Grey BN(M): Brown VT(M): Purple RD : Red BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral DUCTIMAX TECHNICAL MANUAL...
Page 25
» MCB V dm 2-5 WH(M): White = Neutral BK(M): Black BU(M): Blue GY(M): Grey BN(M): Brown VT(M): Purple RD : Red YE(M): Yellow GN(M): Green BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 26
» MCB V DM 6 WH(M): Bianco BK(M): Black BU(M): Blue GY(M): Grey RD : Red BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral DUCTIMAX TECHNICAL MANUAL...
Page 27
» MCB V + RE DM 1 WH(M): White = Neutral BK(M): Black BU(M): Blue GY(M): Grey BN(M): Brown VT(M): Purple RD : Red WH(VC/H): White = valve actuator neutral UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 28
» MCB V + RE DM 2-5 WH(M): Bianco = neutro BK(M): Black GY(M): Grey YE(M): Yellow BU(M): Blue GN(M): Green BN(M): Brown RD : Red WH(VC/H): White = valve actuator neutral DUCTIMAX TECHNICAL MANUAL...
Page 29
» MCB V + RE DM 6 WH(M): White = Neutral BK(M): Black BU(M): Blue GY(M): Grey RD : Red WH(VC/H): White = valve actuator neutral UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 30
» MCM/MCL V DM 1 WH(M): White = Neutral BK(M): Black BU(M): Blue GY(M): Grey BN(M): Brown VT(M): Purple RD : Red BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral DUCTIMAX TECHNICAL MANUAL...
Page 31
» MCM/MCL V DM 2-5 WH(M): White = Neutral BK(M): Black GY(M): Grey YE(M): Yellow BU(M): Blue GN(M): Green BN(M): Brown RD : Red BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 32
» MCM/MCL V DM 6 WH(M): White = Neutral BK(M): Black BU(M): Blue GY(M): Grey RD : Red BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral DUCTIMAX TECHNICAL MANUAL...
Page 33
» MCM/MCL V+RE DM 1 WH(M): White = Neutral BK(M): Black BU(M): Blue GY(M): Grey BN(M): Brown VT(M): Purple RD : Red BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 34
» MCM/MCL V+RE DM 2-5 WH(M): White = Neutral BK(M): Black GY(M): Grey YE(M): Yellow BU(M): Blue GN(M): Green BN(M): Brown RD : Red BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral DUCTIMAX TECHNICAL MANUAL...
Page 35
» MCM/MCL V+RE DM 6 WH(M): White = Neutral BK(M): Black BU(M): Blue GY(M): Grey RD : Red BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 36
» DM 1 TED2T WH(M): White = Neutral VT(M): Purple BK(M): Black RD : Red BU(M): Blue BN (VC/H): Brown = valve actuator line GY(M): Grey BU (VC/H): Blue = valve actuator neutral BN(M): Brown DUCTIMAX TECHNICAL MANUAL...
Page 37
» DM 2-5 TED2T WH(M): White = Neutral GN(M): Green BK(M): Black BN(M): Brown GY(M): Grey RD : Red YE(M): Yellow BN (VC/H): Brown = valve actuator line BU (VC/H): Blue = valve actuator neutral BU(M): Blue UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 38
» DM 6 TED2T WH(M): White = Neutral RD : Red BK(M): Black BN (VC/H): Brown = valve actuator line GY(M): Grey BU (VC/H): Blue = valve actuator neutral BU(M): Blue DUCTIMAX TECHNICAL MANUAL...
Page 39
» DM 1 TED4T WH(M): White = Neutral VT(M): Purple BK(M): Black RD : Red BU(M): Blue BN (VC/H): Brown = valve actuator line GY(M): Grey BU (VC/H): Blue = valve actuator neutral BN(M): Brown UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 40
» DM 2-5 TED4T WH(M): White = Neutral GN(M): Green BK(M): Black BN(M): Brown GY(M): Grey RD : Red YE(M): Yellow BN (VC/H): Brown = valve actuator line BU(M): Blue BU (VC/H): Blue = valve actuator neutral DUCTIMAX TECHNICAL MANUAL...
Page 41
» DM 6 TED4T FLOAT WH(M): White = Neutral RD : Red BK(M): Black BN (VC/H): Brown = valve actuator line GY(M): Grey BU (VC/H): Blue = valve actuator neutral BU(M): Blue UT66002214-05 All copying, even partial, of this manual is strictly forbidden...
Page 42
BN (FLOAT): Brown=pump power supply line VC: Hot water valve (only 4-pipe hydronic indoor unit) BU (FLOAT):Blue = pump power supply neutral VH/RE: Hot water valve (only 4-pipe hydronic indoor unit) or BK (FLOAT): Black = float switch alarm signal heating element DUCTIMAX TECHNICAL MANUAL...
The KP master sleeve can be installed to control with a single control panel up to 4 units (connected in parallel). This accessory is designed for installation on a DIN drive, usually placed on electric board, can be matched with all DUCTIMAX versions.
Page 44
The controller is provided with a programmable display that allows you to view and set the hydronic unit functions by means of the specific interface with parameter description. LED503 - Recess wall-mounted microprocessor control The proposed microprocessor control panels for Galletti indoor units is completed by the LED503 command with LED display that is designed for recess wall mounting. CONTROLLER The control software developed by the Galletti Software Dept., features:...
Page 45
R90/R90C - 90° connection for intake/ delivery Can be installed on both the air inlet and outlet (in the R90C internally insulated version), the 90° fittings can be installed directly on the units. DUCTIMAX. MAFO - Air intake modules with filter Made of galvanized steel sheet, these modules permit to filter the air sucked up by the unit and also to connect the unit to the intake channeling.
Page 46
The trays are made of galvanized metal sheet, with condensate discharge pipe (Ø 17 mm) setup for being connected to a flexible rubber tube, like that which has been envisaged for the condensate discharge trays of the basic unit. They are available for: DUCTIMAX units installed horizontally, VRCD.
The motor requires no maintenance since it has self-lubricating The maintenance requirements of DUCTIMAX ducted units are bearings. 15.1 CLEANING THE AIR FILTER Disconnect the unit from the power supply by setting the main 2.
Page 48
» MAFO - standard air intake » Air intake MAF90-MAFO90 DUCTIMAX TECHNICAL MANUAL...