05.2005
X100 - 24 V output,
The unit has a 24 V voltage output via which power can be supplied to
USS bus
up to three connected inverters.
The USS bus connection is linked to the internal 9-pole SUB D socket
of the serial interface and is provided for looping the USS bus.
15 kW rectifier unit
Terminal
33
34
35
36
50 kW / 100 kW
rectifier units
Connectable cross-section: 2.5 mm² (AWG 12)
33
Terminal 33 is at the top when installed.
34
35
36
Table 7-8
X320 - Serial
On the front panel there is a 9-pole SUB D socket which can be
interface
coupled with the USS bus of the connected inverters through the
connection X100, terminals 35 and 36.
The electronics of the rectifier unit is not linked to the interface.
The rectifier unit does not have a master or slave function.
NOTE
This interface is not provided for the start-up of the connected inverters!
If the X320 interface is to be used, the USS bus connection must be
formed (loop through rectifier unit X100 terminal 35, 36 to all inverters
X100 terminal 35, 36).
The interface cannot be operated until start-up of the inverters has
been completed (addressing of slaves has been carried out).
The following can be connected to the X320 interface:
♦ The OP1S operator control panel (pluggable with a catch-lock in the
♦ A PC with the DriveMonitor program,
♦ Or a higher-level control system.
♦ Only one unit with a master function may be connected-up to the
WARNING
♦ If a unit (e.g. PC with DriveMonitor) is connected up to the RS232
Siemens AG
6SE7087-2NP85-0AA0
SIMOVERT MASTERDRIVES
Designation
33
+24 V (out)
34
0 V
35
RS485P (USS)
36
RS485N (USS)
External 24 V supply, USS bus
front panel) for visualization (display) and operator control of the
connected inverters,
entire USS bus (OP1S or PC or higher-level control).
interface of the inverters (at X103), no unit with a master function
may be connected up at the entire USS bus.
Operating Instructions
Connecting-up
Meaning
Range
24 V voltage output
DC 24 V
Reference potential
USS bus connection
RS485
USS bus connection
RS485
0 V
7-9