SUN2000 (8KTL-28KTL)
User Manual
Alarm ID
Name
326
Abnormal
Grounding
400
System
Fault
410
Abnormal
Auxiliary
Power
504
Version
Mismatch
505
Firmware
Upgrade
Failed
61440
Flash Fault
Issue 12 (2019-06-30)
Severity
Causes
ventilation.
The ambient temperature is
too high.
The internal fan is not
working.
Major
Cause ID = 1
The neutral wire or PGND
cable is not connected to
the SUN2000.
The isolation transformer is
not connected to the
SUN2000 at the output side
when the PV strings are
grounded.
Major
Cause ID = 1/3/21/23/27
An unrecoverable fault has
occurred on a circuit inside the
SUN2000.
Major
Cause ID = 4
The sampling control board
has an abnormal voltage,
which may be caused by the
following:
The internal power chip of
the sampling control board
is faulty.
The detection circuit
becomes faulty.
Minor
Cause ID = 1/2/3
The version of the software
loaded during a software
upgrade is incorrect.
Major
Cause ID = 1
The upgrade is incomplete.
Minor
Cause ID = 1
There is insufficient space
on the flash drive.
The flash drive has bad
blocks or is faulty.
Copyright © Huawei Technologies Co., Ltd.
Measures
ambient temperature exceeds the
upper threshold, improve the
ventilation and heat dissipation.
3. If the ventilation and ambient
temperature both meet
requirements, contact Huawei
technical support.
1. Check that the neutral wire and
PGND cable are properly
connected.
2. If the PV string output is
grounded, check that the
SUN2000 output side connects to
an isolation transformer.
Turn off the AC output switch and
DC input switch. Then turn on the
AC output switch and DC input
switch after 5 minutes. If the fault
persists, contact Huawei technical
support.
1. When the alarm is generated, the
SUN2000 shuts down
automatically. When the fault is
rectified, the SUN2000 starts
automatically.
2. If the alarm occurs repeatedly,
contact Huawei technical
support.
Check whether a recent software
upgrade has been performed. If so,
upgrade the software again to the
correct version.
Upgrade again.
1. Replace the monitoring board.
2. If the monitoring board is built
into the monitoring device,
replace the monitoring device.
8 Maintenance