Produal HDK User Manual page 8

Duct co2 transmitter/controller
Table of Contents

Advertisement

Cont
OFF
OK
Cont
CO2
CONTROLLER
M
Cont
TEMPERATURE
Cont
HUMIDITY
Cont
MAXIMUM CTRL
Parameter
Available values
Cont
OFF / CO2 /
TEMPERATURE /
HUMIDITY / MAXIMUM
CTRL
Control mode
P / PI
Integr. time s
50...5000
CO2 Setpoint
400...10000
CO2 Propor.
100...10000
band
°C Setpoint
0...50.0
°C Propor. band 1.0...32.0
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com
Published: 28.08.2019
OK
OK
OK
PI
300
Modbus ID
Control mode
Integr. time s
OK
P
Control mode
OK
OK
PI
Modbus ID
300
Control mode
Integr. time s
OK
P
Control mode
OK
OK
PI
300
Modbus ID
Control mode
Integr. time s
OK
P
Control mode
OK
OK
PI
300
Modbus ID
Control mode
Integr. time s
OK
P
Control mode
OK
21.0
2.0
°C Setpoint
°C Propor. band
Description
Controlled value.
OFF
CO2
TEMPERATURE
HUMIDITY
MAXIMUM CTRL
Control method.
Integration time (s).
Set point for CO
steps.
Proportional band for CO
10 ppm steps.
Set point for temperature (°C). The value can be adjusted by 0,1 °C
steps.
Proportional band for temperature (°C). The value can be adjusted
by 0,1 °C steps.
Information is subject to change without prior notice.
OK
OK
700
500
CO2 Setpoint
CO2 Propor. band
OK
OK
21.0
2.0
°C Setpoint
°C Propor. band
OK
OK
50
50
%RH Setpoint
%RH Propor. band
OK
OK
700
500
CO2 Setpoint
CO2 Propor. band
OK
OK
50
50
%RH Setpoint
%RH Propor. band
Controller off
CO
2
Temperature
Relative humidity, RH models
Maximum selection control. See more
details after the table.
(ppm). The value can be adjusted by 10 ppm
2
(ppm). The value can be adjusted by
2
8 (15)