Commissioning; Wiring; Selecting Information To Be Viewed On The Display; Calibration - Produal HDK User Manual

Duct co2 transmitter/controller
Table of Contents

Advertisement

1 Commissioning

1.1 Wiring

CAUTION: Device wiring and commissioning can only be carried out by qualified
professionals. Always make the wirings while the power is switched off.
0...10 V, humidity (RH models)
Modbus, RS-485
(M models)

1.2 Selecting information to be viewed on the display

The measurement values scroll on the N model display by default.
Note: In M models, the shown measurement information can be selected also via Modbus.
• Press the S1 button to stop the scrolling to the currently displayed value.
A
A. S1 button
• Press the S1 button again to start the scrolling.

1.3 Calibration

The device uses automatic CO
eliminates the possible long term drift. The automatic calibration function can be used when the CO
concentration drops at least two times within a week to the level of approximately 400 ppm. Therefore
the automatic calibration is effective in spaces that are not continuously occupied.
The automatic calibration function can be deactivated in continuously occupied spaces by using ML-SER
tool.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com
Published: 28.08.2019
24 Vac/dc
0 Vac
0...10 V, CO
2
0...10 V, temperature
0...10 V, controller output
G0
24 Vac 1 A, relay (HD-R)
G
G0
Y1
PWR
Y2
RX
Y3
TX
Y4
REL
A+
B-
BUS
NO
TERM
NC
measurement calibration function (ABC algorithm). The function
2
Information is subject to change without prior notice.
G
G0
Y1
Y2
Y3
Y4
A+
B-
NO
NC
COM
3 (15)
2
EN - 1135050ug

Advertisement

Table of Contents
loading

Table of Contents