Parameter
Available values
Offset CO2ppm
-200...200
ABC-Logic
On / Off
Offset °C
-3,0...3,0
Offset %RH
-5...5
ML-SER tool display shows how much the current value is tuned. The measured value is shown in
brackets after the tuning value.
1.4.2.3 Output menu
You can change the output scaling of all outputs and the controller output direction through the output
menu. Also, the fixed controller output value and duration can be selected through the menu.
OK
0-10V
Modbus ID
Y1-Y4 range
OUTPUT
M
Parameter
Available values
Y1-Y4 range
0-10V / 2-10V / 0-5V
Output mode
Direct / Reversed
Fixed output
OFF / 100% / 75% /
50% / 25% / 0%
Deactivation
6h / 12h / 24h /
MANUAL
1.4.2.4 Controller menu
The control output can be controlled either according to a one measurement value or according to the
maximum selection of all values.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com
Published: 28.08.2019
Description
CO
measurement tuning. The value can be adjusted by 10 ppm
2
steps.
Automatic calibration function (On/Off).
Temperature measurement tuning. The value can be adjusted by
0,1 °C steps.
Humidity measurement tuning, RH models. The value can be
adjusted by 1 % steps.
OK
OK
Direct
OFF
Output mode
Fixed output
100%
Fixed output
Description
Output scaling.
Controller output direction.
Fixed output.
Fixed output deactivation timer.
Information is subject to change without prior notice.
OK
OK
OK
12h
Deactivation
7 (15)