Duct co2 transmitter/controller
Table of Contents

Advertisement

900
Measurement
ppm
M
OK
Modbus-
Modbus
valikko
menu
COMMUNICATIONS
M
OK
Calibration
Kalibrointi-
valikko
menu
CALIBRATION
M
OK
Output
menu
OUTPUT
M
OK
Controller
menu
CONTROLLER
M
The diagram continues on the next page.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com
Published: 28.08.2019
OK
OK
1
9.6
Modbus ID
MODBUS ID
Baud rate (k)
Modbus address
Modbus speed
[OFF / 1...247]
[9.6 / 19.2 / 38.4]
OK
OK
0 (900)
On
Modbus ID
Offset: CO2ppm
ABC-Logic
CO
measurement
ABCLogic calibration
2
tuning [±200 ppm]
[On / Off]
OK
OK
0-10V
Direct
Modbus ID
Y1-Y4 range
Output mode
Output scaling
Controller output direction
[0-10V / 2-10V / 0-5V]
[Direct / Reversed]
OK
Cont
OFF
OK
OK
Cont
PI
Modbus ID
CO2
Control mode
Control method
[PI / P]
OK
P
Control mode
OK
OK
Cont
PI
Modbus ID
TEMPERATURE
Control mode
Control method
[PI / P]
OK
P
Control mode
OK
OK
Cont
PI
Modbus ID
HUMIDITY
Control mode
Control method
[PI / P]
OK
P
Control mode
OK
OK
Cont
PI
Modbus ID
MAXIMUM CTRL
Control mode
Control method
[PI / P]
OK
P
Control mode
OK
21.0
°C Setpoint
°C set point
[0...50 °C]
Information is subject to change without prior notice.
OK
n
Parity
Parity bit
[None / Even / Odd]
OK
0.0 (22.6)
0 (30)
Offset: °C
Offset: %RH
Temperature measurement
Humidity measurement
tuning [±3.0 °C]
tuning [±5 %RH]
OK
OFF
Fixed output
OK
100%
12h
Fixed output
Deactivation
Fixed output
Fixed output deactivation
[100 / 75 / 50 / 25 / 0 %]
timer [6 / 12 / 24 h / MANUAL]
OK
300
700
Integr. time s
CO2 Setpoint
Integration time
CO
set point
2
[50...5000 s]
[400...10000 ppm]
OK
300
21.0
Integr. time s
°C Setpoint
Integration time
°C set point
[50...5000 s]
[0...50 °C]
OK
300
50
Integr. time s
%RH Setpoint
Integration time
%RH set point
[50...5000 s]
[0...100 %]
OK
300
700
Integr. time s
CO2 Setpoint
CO
Integration time
set point
2
[50...5000 s]
[400...10000 ppm]
OK
50
2.0
°C Propor. band
%RH Setpoint
° C proportional band
%RH set point
[1.0...32.0]
[0...100 %]
OK
OK
OK
OK
500
CO2 Propor. band
CO
proportional band
2
[100...10000]
OK
OK
2.0
°C Propor. band
° C proportional band
[1.0...32.0]
OK
OK
50
%RH Propor. band
%RH proportional band
[10...100]
OK
OK
500
CO2 Propor. band
CO
proportional band
2
[100...10000]
OK
OK
50
%RH Propor. band
%RH proportional band
[10...100]
5 (15)
EN - 1135050ug