Pipe Insulation - Samsung AM MXVAFC Series Installation Manual

Table of Contents

Advertisement

Pipe insulation

Insulating the refrigerant pipes and branch joints
f Check for gas leakage before completing (the hose and pipe insulation) and if there is no sign of leakage, make sure to
f
insulate the pipes and hoses .
f Use EPDM material insulator that meets the following conditions .
f
Test item
Density
Dimensional change rate by heat
Absorption rate
Thermal conduction rate
Moisture transpiration factor
Moisture transpiration grade
Formaldehyde dispersion
Oxygen rate
Selecting the refrigerant pipe insulator
f Insulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size .
f
f The standard condition is; temperature at 30°C, humidity less than 85% . If case if the humidity is higher, you must
f
increase the size by one grade as stated in below table .
Outer diameter
Pipe
mm
6 . 3 5~9 . 5 2
Liquid pipe
12 . 7 ~50 . 8
6 . 3 5
9 . 5 2~25 . 4
Gas pipe
28 . 5 8~44 . 4 5 1 1/8~1 3/4
50 . 8
❋ ❋ When installing insulation in places and conditions below, use the same insulation that is used for high humidity
conditions .
<Geological condition>
- High humidity places such as shoreline, hot spring, near lake or river, and ridge (when the part of the building is
covered by earth and sand . )
<Operation purpose condition>
- Restaurant ceiling, sauna, swimming pool etc .
<Building construction condition>
- The ceiling frequently exposed to moisture and cooling is not covered . (e . g . The pipe installed at a corridor of a
dormitory and studio or near an exit that opens and closes frequently . " )
- The place where the pipe is installed is highly humid due to the lack of ventilation system .
ng/(m
g/(m
General
[ 30ºC (86ºF), 85% ]
inch
mm
1/4~3/8
9
1/2~2
13
1/4
13
3/8~1
19
19
2
25
Unit
g/cm
3
%
g/cm
3
W/m·K
·s·Pa)
2
2
·24h)
mg/L
%
Insulator (Cooling)
High humidity
[ 30ºC (86ºF), over 85% ]
EPDM, NBR
inch
mm
3/8
9
1/2
13
1/2
19
3/4
25
3/4
32
1
38
Standard
0 . 0 48~0 . 0 96
Below -5
Below 0 . 0 05
Below 0 . 0 37
Below 15
Below 15
There should be none
Over 25
Remarks
inch
3/8
1/2
Heating resisting
3/4
temperature over
1
120°C(248°F)
1 1/4
1 1/2
73