Refrigerant pipe installation
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch .
❋ ❋ However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to the outdoor
unit (A), apply the pipe size (A) .
Indoor unit capacity [kW (MBH)]
15 . 0  kW (51 . 2  MBH) and below
Over 15 . 1  kW~22 . 4  kW
(51 . 3 ~ 76 . 4  MBH) and below
Over 22 . 5  kW~28 . 1  kW
(76 . 5 ~ 95 . 9  MBH) and below
Over 28 . 2  kW~40 . 0  kW
(96 . 0 ~ 136 . 5  MBH) and below
Over 40 . 1  kW~45 . 0  kW
(136 . 6 ~ 153 . 5  MBH) and below
Over 45 . 1  kW~63 . 3  kW
(153 . 6 ~ 216 . 0  MBH) and below
Over 63 . 4  kW~70 . 3  kW
(216 . 1 ~ 239 . 9  MBH) and below
Over 70 . 4  kW~98 . 4  kW
(240 . 0 ~ 335 . 8  MBH) and below
Over 98 . 5  kW~135 . 2  kW
(335 . 9 ~ 461 . 3  MBH) and below
Over 135 . 3  kW~169 . 0  kW
(461 . 4 ~ 576 . 7  MBH) and below
Over 169 . 0  kW (576 . 7  MBH)
Note1) Note on measuring distance between branch joints (B) : You must measure the distance between first branch joint
to the last indoor unit . (NOT from first joint to the last branch joint
Note2) If Ø 25 . 4 0 mm (Ø 1") pipe is not available on site, use Ø 28 . 5 8 mm (Ø 1 1/8") pipe .
Note3) If Ø 31 . 7 5 mm (Ø 1 1/4") pipe is not available on site, use Ø 34 . 9 2 mm (Ø 1 3/8") pipe .
Note4) If Ø 38 . 1 0 mm (Ø 1 1/2") pipe is not available on site, use Ø 41 . 2 8 mm (Ø 1 5/8") pipe .
40
Branch pipe length within 45 m
(147.64 ft)
note1)
Liquid pipe
Gas pipe
[mm (inch)]
[mm (inch)]
Ø 15 . 8 8 (5/8)
Ø 19 . 0 5 (3/4)
Ø 9 . 5 2 (3/8)
Ø 22 . 2 2 (7/8)
Ø 12 . 7 0 (1/2)
Ø 28 . 5 8 (1 1/8)
Ø 15 . 8 8 (5/8)
Ø 34 . 9 2 (1 3/8)
Ø 19 . 0 5 (3/4)
Ø 41 . 2 8 (1 5/8)
Ø 22 . 2 2 (7/8)
Ø 53 . 9 8 (2 1/8)
Branch pipe length between 45~90 m
(147.64~295.28 ft)
Liquid pipe
Gas pipe
[mm (inch)]
[mm (inch)]
Ø 19 . 0 5 (3/4)
Ø 22 . 2 2 (7/8)
Ø 12 . 7 0 (1/2)
Ø 25 . 4 0 (1)
Ø 28 . 5 8 (1 1/8)
Ø 15 . 8 8 (5/8)
Ø 31 . 7 5 (1 1/4)
Ø 19 . 0 5 (3/4)
Ø 38 . 1 0 (1 1/2)
Ø 22 . 2 2 (7/8)
Ø 41 . 2 8 (1 5/8)
Ø 53 . 9 8 (2 1/8)
Ø 25 . 4 0 (1)
note2)
note1)
note2)
note3)
note4)