Extech Instruments PQ3450-2-NIST User Manual page 14

3-phase power analyzer/datalogger
Table of Contents

Advertisement

4.5.6 Potential Transformer (PT) Setup
1.
In the Setup Mode, use the up and down arrow keys to scroll to the PT field.
2.
Press SHIFT, the display "SHIFT1" will switch ON
3.
Use the ▲ or ▼ keys to adjust the PT value (the range is 1 to 1000)
4.
Press SHIFT again to return to Setup Mode editing or press EXIT to leave the Setup mode.
4.5.7 Current Transformer (CT) Setup
1.
In the Setup Mode, use the up and down arrow keys to scroll to the CT field.
2.
Press SHIFT, the display "SHIFT1" will switch ON
3.
Use the ▲ or ▼ keys to adjust the CT value (the range is 1 to 600)
4.
Press SHIFT again to return to Setup Mode editing or press EXIT to leave the Setup mode.
4.5.8 Audible Beeper ON/OFF
1.
In the Setup Mode, use the up and down arrow keys to scroll to the BEEP field.
2.
Press SHIFT, the display "SHIFT1" will switch ON
3.
Use the ▲ or ▼ keys to select ON or OFF
4.
Press SHIFT again to return to Setup Mode editing or press EXIT to leave the Setup mode.
4.5.9 SD Card Numerical Format (USA or European)
Note: SD Memory Cards default to the basic numerical format (USA) whereby a period is used
to separate units from tenths, for example: 20.00. European formatting uses a comma (for
example: 20,00).
1.
In the Setup Mode, use the up and down arrow keys to scroll to the DECIMAL field.
2.
Press SHIFT, the display "SHIFT1" will switch ON
3.
Use the ▲ or ▼ keys to select the desired format USA (.) or EURO (,).
4.
Press SHIFT again to return to Setup Mode editing or press EXIT to leave the Setup mode.
14