PIR lighting management sensor - High ceiling areas
1. USE
This device allows a light source to be controlled automatically by
detecting movement in a monitored area.
It can be installed in high ceiling areas (gymnasium, storage area, etc).
Motion sensor with 360° detection angle.
Detection type: infrared (PIR)
Mounting type: ceiling
2. TECHNICAL CHARACTERISTICS
Voltage: 100 - 240 V~
Frequency: 50/60 Hz
No-load power consumption: 0.6 W
Output via normally open contact connected to the phase
Drilling diameter: 122 mm without flush-mounting box
Wiring: 2 x 2.5 mm
2
Number of terminals: 4
Terminal type: screwless
Stripping length: 8 mm
Weight: 230 g
Impact resistance: IK04
Penetration by solid and liquid matter: IP55
Usage temperature: - 25°C to + 45°C
Storage temperature: - 25°C to + 70°C
230 V~
2000 W
8.5 A
1000 VA
110 V~
1000 W
8.5 A
500 VA
1 - Halogen bulbs
2 - ELV halogen, compact fluorescent and fluorescent bulbs with
separate electronic ballast
3 - ELV halogen, compact fluorescent and fluorescent bulbs with
separate ferromagnetic ballast
4 - Fluorescent tubes
Technical data sheet: S000081479EN_2
IP66 with cable gland
4.3 A
1000 VA
4.3 A
10x(2x36 W)
4.3 A
500 VA
4.3 A
5x(2x36 W)
Updated: 06/09/2022
CONTENTS
1. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Technical characteristics. . . . . . . . . . . . . . . . .1
3. Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
4. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
5. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
6. Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
7. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
8. Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
9. Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . .7
10. Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
11. Standards and certifications . . . . . . . . . . . . .7
12. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .8
2. TECHNICAL CHARACTERISTICS (continued)
Products approved for 40,000 operations
Mains zero breaking: in order to limit the effect of induced currents on
cut-off relays by fluorescent loads in particular, this sensor breaks the
voltage at mains zero. Switching occurs when the voltage is at point 0
which ensures a longer life for sources and for the sensor.
LEARN LED
Sensor/PIR
sensor
4.3 A
250 W
1 A
250 W
4.3 A
125 W
1 A
125 W
5 - Compact fluorescent bulbs with built-in electronic ballast
6 - Compact fluorescent bulbs with built-in ferromagnetic ballast
7 - LED bulbs
8 - Contactor
Cat. No(s): 0 489 32
LEARN button
Light level
cell
Detection
LED
1 A
250 W
1 A
500 VA
1 A
125 W
1 A
250 VA