LEGRAND 0 488 14 Quick Start Manual
LEGRAND 0 488 14 Quick Start Manual

LEGRAND 0 488 14 Quick Start Manual

Switch sensor - rf pir surface mounted

Advertisement

Quick Links

Switch sensor - RF PIR surface mounted

1. USE

This device allows a light source to be controlled automatically through the
detection of movement in the surveillance zone.
Motion sensor with horizontal detection angle of 270°
Vertical orientation: 90°
Detection type: infrared (PIR)
Mounting type: wall and ceiling

2. TEChNICal ChaRaCTERISTICS

Voltage: 100-230 V~
Frequency: 50/60 Hz
No-load power consumption: 0.74 W
Output via normally open contact connected to the phase
Wiring: 2 x 2.5 mm
2
Surface mounted
Weight: 205 g
Impact resistance: IK04
Penetration by solid and liquid matter: IP55
Operating temperature: -5°C to +45°C
Storage temperature: -20°C to +70°C
Technology: radio frequency 2.4 GHz - Zigbee certified product -
Manufacturer Specific Profile - Wireless network mesh
AUX GROUP button
NETWORK button
NETWORK LED
IR reception LED
LEARN LED
Learn bUTTON
Green detection indicator
LIGHT GROUP button
1
230 V~
2000 W
8.5 A
110 V~
1000 W
8.5 A
Technical data sheet: S000079749-EN
CONTENTS
2
3
2000 W
8.5 A
1000 VA
1000 W
8.5 A
500 VA
Updated on:
87045 LIMOGES Cedex
Telephone: +33(0)5 55 06 87 87 - Fax: +33(0)5 55 06 88 88
Cat. No(s): 0 488 14

3. DImENSIONS

1
Incandescent bulb
2
Tungsten halogen bulb
3
Tungsten halogen bulb with separate ferromagnetic transformer or electronics
4
Fluorescent tubes
5
Compact fluorescent bulbs with built-in ECGs
6
Compact fluorescent bulbs with separate ferromagnetic or electronic ballast
7
Contactors
4
5
4.3 A
10x(2x36 W)
4.3 A
500 VA
4.3 A
5x(2x36 W)
4.3 A
250 VA
CONTENTS
1. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Technical characteristics. . . . . . . . . . . . . . . . . .1
3. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
4. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
5. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
6. Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
7. Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
8. Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
9. Standards And Certifications . . . . . . . . . . . . . .4
166
6
7
2.1 A
1000 VA
4.3 A
I max. o 2A
2.1 A
500 VA
4.3 A
Created: 17/05/2013
Page
1/4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 0 488 14 and is the answer not in the manual?

Questions and answers

Summary of Contents for LEGRAND 0 488 14

  • Page 1 87045 LIMOGES Cedex Telephone: +33(0)5 55 06 87 87 - Fax: +33(0)5 55 06 88 88 Switch sensor - RF PIR surface mounted Cat. No(s): 0 488 14 CONTENTS Page 1. Use ........1 2.
  • Page 2 Switch sensor - RF surface mounted PIR Cat. No(s): 0 488 14 5. INSTallaTION 4. CONNECTION Number of terminals: 4 Wall Terminal type: screwless Terminal capacity: 2x2.5 mm Stripping length: 8 mm Wiring with auxiliary control: manual on/auto off Pressing the auxiliary control enables the load to be switched on or off manually.
  • Page 3 Switch sensor - RF surface mounted PIR Cat. No(s): 0 488 14 6. SETTINgS 6. SETTINgS (continued) - modifying parameters with configuration tools (for details of Sensor parameter Default modifiable Configuration configuration, see legrandoc.fr) value parameters tools 0 882 0 882 3, 5, 10, 15, 20 min −...
  • Page 4 Switch sensor - RF surface mounted PIR Cat. No(s): 0 488 14 8. CaRE Keep the lens clean. Clean the surface with a cloth. Do not use: acetone, tar-removing cleaning agents or trichloroethylene. Resistant to the following products: - Hexane (EN 60669-1)

Table of Contents