Appendix A - Modbus Communication Port Setting
Table 11. Remote Control.
Control
Group
Definition
Reset
Reset trip
Reset powered up indication
Reset peak demand watts
Reset energies
Reset operations count
Reset runtime
Reset all min/max values
Reset min/max currents
Reset min/max line-to-line voltages
Reset min/max line-to-neutral voltages 0
Reset trip count
Reset temperature
Reset all diagnostics information
Control
Group
Definition
Open/Close
Open Breaker (for 2 seconds
Breaker
opens relay which is assigned
to function "Open Command")
Close Breaker (for 2 seconds
closes relay which is assigned
to function "Close Command")
Relay Remote
Relay Output
Control
A.3.8 Date and Time
The trip unit supports Modbus master to read real-time clock
information. Eight registers, starting from register number
402921, are used for this information, as defined in Table
A10. Detailed information is listed in Table A12.
Table 12. Real Time Clock
Modbus Register
Definition
Number
Month
402921
Day
402922
Year
402923
Day of week
402924
Hour
402925
Minute
402926
Second
402927
1/100th second
402928
40
PT UNIT USER MANUAL APRIL 2023 www.eaton.com.cn
Byte 2 Byte 1 Byte 0
0
0
2
0
0
3
0
0
4
0
0
8
0
1
2
0
1
3
0
1
4
0
1
13
0
1
14
1
15
0
5
1
0
5
2
0
5
3
Byte 2 Byte 1
Byte 0
1
0
0
1
0
1
4
1: Enabled
1: Relay 1
2: Disabled
2: Relay 2
3: Relay 3
Modbus Register
Address
Data Range
0x0B68
1-12
0x0B69
1+31
0x0B6A
1 = Sunday
0x0B6B
7 = Saturday
0x0B6C
0-23
0x0B6D
0-59
0x0B6E
0-59
0x0B6F
A.3.9 Internal Diagnosis
The trip unit supports internal Modbus diagnostics to moni-
tor internal Modbus port communication with function code
08. For different sub-function codes, diagnostics informa-tion
is listed in Table A13.
Table A13. Diagnostics.
Sub-function code
Action
0
Echo query
1
Restart communication
4
Force listen
10
Clear counters
11
Modbus UART bus message count
12
Modbus UART CRC error count
13
Exception count
14
Slave message count
15
Slave no response count
16
Slave NAK count
17
Slave busy count
18
Modbus UART over run error count
20
Clear Modbus UART counters
23
Modbus UART framing error count
24
Modbus UART noise error count
25
Modbus UART parity check error count
26
MCU1 Firmware Version
27
MCU1 Firmware Reversion
28
MCU1 Firmware Build
29
MCU2 Firmware Version
30
MCU2 Firmware Reversion
31
MCU2 Firmware Build
32
MCU3 Firmware Version
33
MCU3 Firmware Reversion
34
MCU3 Firmware Build
35
USB Version
36
USB Reversion
37
Reset block of registers