Eaton PT 10 Instruction Manual page 31

Power trip (pt) units
Hide thumbs Also See for PT 10:
Table of Contents

Advertisement

Each data object occupies two registers (four bytes) in length, except for certain energy objects. These energy objects occupy
four registers. Since these objects have the capability to change in real time, a complete data object must be obtained in a
single transaction to avoid data tearing. Attempting to access a partial data object will result in an exception code 84. (See
Section A.3.11)
Table A3. Real Time Data
Register Number.
Register Addresses (HEX)
IEEE Float
Fixed Point (FP) IEEE Float
404609
406145
1200
404611
406147
1202
404613
406149
1204
404615
406151
1206
404617
406153
1208
404619
406155
120A
404623
406159
120E
404625
406161
1210
404627
406163
1212
404631
406167
1216
404633
406169
1218
404635
406171
121A
404651
406187
122A
404653
406189
122C
404655
406191
122E
404659
406195
1232
404661
406197
1234
404697
406233
1258
404719
406255
126E
404721
406257
1270
406259
406261
406263
406271
404765
406301
129C
406305
406309
406313
406329
404797
406333
12BC
404799
406335
12BE
404835
406371
12E2
404837
406373
12E4
404839
406375
12E6
404843
406379
12EA
404845
406381
12EC
Objects
Fixed Point (FP)
Descriptions
1800
Status cause:
404609 and 406415 high byte is primary status, shown in Table A14.
404609 and 406415 low byte is secondary status, shown in Table A15.
404610 and 406416 are cause-of-status, shown in Table A16.
1802
IA
1804
IB
1806
IC
1808
IG
180A
IN
180E
VAB
1810
VBC
1812
VCA
1816
VAN
1818
VBN
181A
VCN
182A
Real 3 phase power
182C
Reactive 3 phase power
182E
Apparent 3 phase power
1832
Power factor
1834
Frequency
1858
Real power peak demand
186E
Product ID
1870
Frequency
1872
Forward energy
1874
Reverse energy
1876
Total energy
187E
Apparent energy
189C
Temperature
18A0
Forward energy
18A4
Reverse energy
18A8
Total energy
18B8
Apparent energy
18BC
Reactive power peak demand
18BE
Apparent power peak demand
18E2
Phase A current demand
18E4
Phase B current demand
18E6
Phase C current demand
18EA
Phase N current demand
18EC
Real power demand
Appendix A - Modbus Communication Port Setting
PT UNIT USER MANUAL APRIL 2023 www.eaton.com.cn
FP Data
Units
Factor
A
10
A
10
A
10
A
10
A
10
V
10
V
10
V
10
V
10
V
10
V
10
W
1
VAR
1
VA
1
100
Hz
10
W
1
Hz
100
KWh
1
KWh
1
KWh
1
kVAh
1
°C
1
Wh
1
Wh
1
Wh
1
Vah
1
VAR
1
VA
1
A
1
A
1
A
1
A
1
W
1
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pt 20Pt 25

Table of Contents