Eaton PT 10 Instruction Manual page 36

Power trip (pt) units
Hide thumbs Also See for PT 10:
Table of Contents

Advertisement

Appendix A - Modbus Communication Port Setting
Table A4. Setpoints Group 0: System Group (continued)
Bit
Mask
Register
Field
Field
403019
0
0x0001
403020
7-0
0x00FF
403021
7-0
0x00FF
403022
11-0
0x0FFF
403023
0
0x0001
403024
0
0x0001
32
PT UNIT USER MANUAL APRIL 2023 www.eaton.com.cn
Setpoint Name
Demand Window Setpoint
Demand Interval
Breaker Health Alarm Threshold
System Voltage
Neutral Transformer Style
Ground Sensor Style
R/W
Format
Value Definition
R/W
Encoded
0 = Fixed
1 = Sliding
R/W
Unit: Minute (5 to 60 minutes)
R/W
Unit: Percentage (50 to 100)
R/W
Unit: Volt (208 to 690)
R
Encoded
0 = Rogowski coil
1 = Current sensor
R
Encoded
0 = Rogowski coil
1 = Current sensor

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pt 20Pt 25

Table of Contents